User Manual
Universal Serial/PROFIBUS DP Gateway
GT200-DP-RS
WWW.SSTCOMM.COM
17
After you finish the DP slave configuration, click “OK”.
(2) Add modules to the device.
Select the GT200-DP-RS device on the DP bus, then double click on the modules you want to add to in the
catalog. The added module is on the slot of the GT200-DP-RS device. Please select the appropriate modules
according to the address area you want to read/write.
Note:
The max number of modules is 64. Maximum input byte: 244. Maximum output bytes: 244.
(3) Configure the module parameters. Double click on a module to open the parameters window.
For example, for the module “Read 1 Word (4xxxx)”, set the DP Input address in the “Address / ID” .