5.4 Data Mapping in Software Configuration Mode
In the “Software Configuration” mode, the data mapping address can be manually configured. The data mapping
relationship between GT200-DP-RS buffer and PROFIBUS DP is shown below. The address N and M (or X and
Y) can be discontinuous number.
PROFIUS DP
Input Address
GT200-DP-RS
Input Buffer
PROFIUS DP
Output Address
GT200-DP-RS
Output Buffer
Module 1
N
0000H
Module 3
X
4000H
N+1
0001H
X+1
4001H
Module 2
M
0002H
X+2
4002H
M+1
0003H
X+3
4003H
M+2
0004H
Module 4
Y
4004H
M+3
0005H
Y+1
4005H
...
...
...
...
...
...
For example, in STEP7, add the following modules on the slot. The I address corresponds to input buffer data and
the Q address corresponds to output buffer.
The IB274~281 corresponds to 0000H~0007H of GT200-DP-RS input buffer. The IB300 of next input module
corresponds to 0008H.
The QB272~QB279 can corresponds to 4000H~4007H of GT200-DP-RS output buffer. The QB326~327 of next
output module corresponds to 4009H~400AH.