4.3. Electrical connection

 

 

SDIS sensor is equipped with a 14-pin connector Amphenol PT. 
Specification of Lapp Cable Ölflex Servo FD770 CP: 

 

Multiple core cable: 6 × 2x0, 25 mm ² and 2 x 0.5 mm ² shielded 

 

Rugged design for industrial applications 

 

Outer diameter: 10.3 mm 

 

Minimum bending radius: 50 mm 

 

Each wire is labeled with a different color 

 

Note: Unused cores must be insulated or connected to free terminals.

 

 

Note: When disconnecting the cable, plug the sensor connector with protective cover for 
          protect the contacts from corrosion.

 

 

 

4.4. Connection of air and water

 

  

Cooling water and cleaning air is fed to the quick couplers cooling housing that is also the sensor 
mounting  stand.  Cooling  housing  is  separately  attached  to  the  sensor,  so  the  sensor  can  be 
replaced  without  disconnecting  the  cooling  water  and  air  and  setting  changes  the  sensor 
mounting. 
 
  

4.4.1. Cooling 
  

The cooling channel housing is positioned, allowing the cooling water sensor. 
Conditions for cooling: 

 

The sensor is recommended to cool at ambient temperatures above 50 ° C. Laboratory 

tests have shown that a properly cooled sensor can operate at temperatures up to 100 °C. 
Specifications of cooling water: 

 

Industrial pure water, maximum temperature 25 ° C 

 

Maximum recommended pressure: 4 bars. 

 

Flow rate: 1 -2 liters / min. 

Cooling circuit: 

 

Material: aluminum cooling groove in the housing. 

 

Connection: Hose diameter 10 mm (for quick couplers). 

 

 

4.4.2. Cleaning air

 

  

Compressed air is used to remove dust on the windscreen in front of the sensor. The system is 
designed to give the high pressure area in front of the sensor. 
System Specifications cleaner air: 

 

Air Quality: Air must be dry, free of grease and dust free 

 

Air pressure: 50 to 120 g / cm ² 

 

Flow: 4-16 l / min. 

 

Connection: Hose 10mm (for quick couplers) 

 

Summary of Contents for SDIS - 1050

Page 1: ...USER MANUAL Universal position sensor and hot metal detector SDIS 1050...

Page 2: ...so that the infrared radiation is reflected to the photocell from each facet of rotating mirror very accurate even in the case when the entire sensing field is covered with hot material Radiation rec...

Page 3: ...ing made of aluminum alloy suport wall with mounting stand adjustable in both directions adapted to the cooling unit with water and blowing air windscreen to prevent pollution connection of water and...

Page 4: ...ndicular to the measured product When selecting the location of the sensor attention to the following must be paid Other source of infrared radiation in addition to the measured material can not inter...

Page 5: ...onnecting the cooling water and air and setting changes the sensor mounting 4 4 1 Cooling The cooling channel housing is positioned allowing the cooling water sensor Conditions for cooling The sensor...

Page 6: ...ron etc The temperature range depends on the infrared radiation of the product Angles standard sensor is supplied with a viewing angle of 50 degrees with a special mask inside the aperture angle can b...

Page 7: ...Operating temperature 10 C to 60 C At an ambient temperature above 40 C it is recommended to cool sensor with industrial water at a temperature up to 25 C pressure of 1 2 bar flow rate of 1 2 l min P...

Page 8: ......

Page 9: ...selected gain Thre 25 selected threshold Mode LS selected operation mode of the sensor LS or HMD Laser 0 press button to light up the targeting laser for 2 minutes Laser 1 Failure message can be flas...

Page 10: ...Set Rel Rel value set is chosen by external relay Man1 measure according ValSet1 Man2 measure according ValSet2 Window Beg 5 beginning of measuring window analog output 4mA position 0 End 95 ending o...

Page 11: ...s setting End 0 90 distance between laser to end of meas window meters Outputs AnOut1 I output signal Analog 1 I intensity P position setting of analog AnOut2 P output signal Analog 2 I intensity P po...

Page 12: ...detection is proportional to material position in the sensor s field of view Additionally sensor can be set to HMD mode hot metal detector sensor only detects if signal from PbS photocell exceeds thr...

Page 13: ...ilters of output signals to improve accuracy or to avoid false detection By adjusting SiUp and SiDo values you can specify how many times signal must be detected befor output detection signal is set o...

Page 14: ...sh pull C gray presence of material detect 24VDC max 50mA H ping neg presence of material detect 0VDC max 50mA M black neg alarm all OK 24VDC max 50mA alarm 0VDC Relay outputs E brown thick w presence...

Reviews: