SSK SDIS - 1050 User Manual Download Page 12

Comm  

-> 

RS232    

-> 

Term  ? 

(

=Noname, VT100, SoftCon

)

 

communication 

 

 

 

type of connection-PC or type of terminal 

settings 

 

 

 

 

Sp=19200 

speed 

 

 

 

 

 

 

Par=None 

parity 

 

 

 

 

 

 

Stop=  1 

stop-bit 

 

 

 

 

 

 

 

RS485    

-> 

Addr=  0

 

address 

 

 

 

 

 

 

Prot=Asc

 

protocol Ascii, RTU 

 

 

 

 

 

 

Sp=19200 

speed 

 

 

 

 

 

 

Par=None 

parity 

 

 

 

 

 

 

Stop=  1 

stop-bit 

 

 
SysInfo 

-> 

SDIS1050 

model number

 

 

 

 

SN:12001 

serial number 

 

 

 

Fw=6.103 

version firmware

 

 

 

 

UT 25.55 

uptime from last power on

 

 

 

 

Tem=35°C 

temperature inside unit (reports alarm after exceeding 
60°C) 

 

Fact.Res 

-> 

Reset  ? 

reset all settings to the original values after confirmation  
(you will be automatically logged off) 

 

Logout 

-> 

Logout ? 

logoff after confirmation (automatically after 10 min)

 

 
Explanation of sensor function and menu items 
 

Mode (LS/HMD)

- sensor mode 

Primary function of sensor is 

LS

 – loop scanner – sensor for position measurement of the edge 

of hot material. In this mode, sensor must be situated so, that the edge of hot material is in his 
field of view. If signal from PbS photocell exceeds threshold, then the edge of this signal is 
used for detection of material position (usually trailing edge). Angle of rotating mirror in the 
moment of detection is proportional to material position in the sensor's field of view. 
Additionally sensor can be set to 

HMD

 mode – hot metal detector – sensor only detects if 

signal from PbS photocell exceeds threshold (menu item 

Thre

). Edge of material does not need 

to be in the field of view. Although basic mask inside the sensor is enough usually to limit 
sensor's field of view, in some cases it needs to be limited by additional mechanical shields (it 
depends on place of installation). Please send us max. viewing angle you need in quotation. 
 

Sensor –

 detection parameters configuration 

There is possibility to configure two parameter value sets (gain, threshold, hysteresis) 
and switch between them (also remotely). This is suitable for production lines with different 
product profiles. E.g. for thin wire it needs to be higher gain then for thick bars  
In each set (

ValSet1

,

ValSet2

) there is possibility to adjust gain (

Gain

), threshold (

Thre

) and 

hysteresis (

HysT

). Sensor sets output detection signal to on if amplitude of photocell signal 

exceeds threshold (

Thre

), and sets it off if amplitude is below 

Thre-HysT

Which value set is actually used can be selected in menu item 

Set

 - manually (item 

Set

 is set to 

Man1

 or 

Man2

) or it can be selected remotely by switching relay (item 

Set

 is set to 

Rel

).  

 
 

Summary of Contents for SDIS - 1050

Page 1: ...USER MANUAL Universal position sensor and hot metal detector SDIS 1050...

Page 2: ...so that the infrared radiation is reflected to the photocell from each facet of rotating mirror very accurate even in the case when the entire sensing field is covered with hot material Radiation rec...

Page 3: ...ing made of aluminum alloy suport wall with mounting stand adjustable in both directions adapted to the cooling unit with water and blowing air windscreen to prevent pollution connection of water and...

Page 4: ...ndicular to the measured product When selecting the location of the sensor attention to the following must be paid Other source of infrared radiation in addition to the measured material can not inter...

Page 5: ...onnecting the cooling water and air and setting changes the sensor mounting 4 4 1 Cooling The cooling channel housing is positioned allowing the cooling water sensor Conditions for cooling The sensor...

Page 6: ...ron etc The temperature range depends on the infrared radiation of the product Angles standard sensor is supplied with a viewing angle of 50 degrees with a special mask inside the aperture angle can b...

Page 7: ...Operating temperature 10 C to 60 C At an ambient temperature above 40 C it is recommended to cool sensor with industrial water at a temperature up to 25 C pressure of 1 2 bar flow rate of 1 2 l min P...

Page 8: ......

Page 9: ...selected gain Thre 25 selected threshold Mode LS selected operation mode of the sensor LS or HMD Laser 0 press button to light up the targeting laser for 2 minutes Laser 1 Failure message can be flas...

Page 10: ...Set Rel Rel value set is chosen by external relay Man1 measure according ValSet1 Man2 measure according ValSet2 Window Beg 5 beginning of measuring window analog output 4mA position 0 End 95 ending o...

Page 11: ...s setting End 0 90 distance between laser to end of meas window meters Outputs AnOut1 I output signal Analog 1 I intensity P position setting of analog AnOut2 P output signal Analog 2 I intensity P po...

Page 12: ...detection is proportional to material position in the sensor s field of view Additionally sensor can be set to HMD mode hot metal detector sensor only detects if signal from PbS photocell exceeds thr...

Page 13: ...ilters of output signals to improve accuracy or to avoid false detection By adjusting SiUp and SiDo values you can specify how many times signal must be detected befor output detection signal is set o...

Page 14: ...sh pull C gray presence of material detect 24VDC max 50mA H ping neg presence of material detect 0VDC max 50mA M black neg alarm all OK 24VDC max 50mA alarm 0VDC Relay outputs E brown thick w presence...

Reviews: