Installation
Waukesha Cherry-Burrell
Page 18
95-03057
October 2005
Suggested Media Piping for Liquid Over Feed Refrigeration
The liquid feed solenoid valve when opened, allows liquid refrigerant to flow into the jacket of the heat exchanger. The
flow is regulated by a manually set flow control valve. Cooling is achieved when the pressure control valve is opened,
causing the pressure in the jacket to be reduced. This causes the liquid refrigerant to change phase, absorbing heat from
the heat exchanger tube and product. The cooling rate is controlled by the back pressure on the system and stops when the
valve is closed. Hot gas is used to push all of the remaining liquid from the system into the ammonia low pressure receiver
and quickly warm the system. The low pressure receiver in the compressor room is designed to separate the liquid from
the vapor before re-compressing.
Table 3: Call Outs For Figure 6
Figure 6 - Suggested Media Piping, Liquid Over Feed or Pumped Refrigeration
1. Safety Relief Valve
10. Dual Pressure Regulating Valve (includes Items 4, 8 and 9)
2. Product IN
11. To Refrigerant Low Pressure Receiver
3. Product OUT
12. Hot Gas Purge Valve
4. Low Pressure Solenoid Valve, see Item 10
13. Flow Control Valve
5. Hot Gas
14. Liquid Feed Solenoid Valve
6/7. Electric Control Signal or Instrument Air
Regulated to 60 PSI
15. Liquid Refrigerant from Low Pressure Receiver
16. Hot Gas Reducing Valve
8. Low Pressure Regulating Valve, see Item 10
17. Hot Gas Solenoid Valve
9. High Pressure Regulating Valve, see Item 10
18. Hot Gas Pressure Regulating Valve
Summary of Contents for Waukesha Cherry-Burrell Votator II
Page 64: ...Parts Lists Waukesha Cherry Burrell Page 64 95 03057 October 2005 Single Mechanical Seal...
Page 66: ...Parts Lists Waukesha Cherry Burrell Page 66 95 03057 October 2005 Double Mechanical Seal...
Page 75: ...Waukesha Cherry Burrell Addendum October 2005 95 03057 Page75 Vertical Refrigeration System...
Page 76: ...Addendum Waukesha Cherry Burrell Page 76 95 03057 October 2005 Horizontal Frame Options...
Page 78: ...Addendum Waukesha Cherry Burrell Page 78 95 03057 October 2005 Vertical Hydraulic Schematic...
Page 83: ......