24
Anybus Option Modules
4.6.2 Baud Rate
The Baud Rate is automatically detected. It is not possible to manually select.
4.6.3 Node Address
The Node Address is set by parameter
202)FBUS
202)FBUS
NODE
NODE
ID
ID
.
Note that a power cycle of the drive may be necessary before a change takes effect.
4.6.4 Cyclic Data
To transfer Cyclic Data (Process Data), the PLC must be configured to match the number of
Input and Output words from the number of used FIELDBUS
GET
GET
FROM
FROM
s and
GOTO
GOTO
s.
The GSD file specifies nine INPUT modules and nine OUTPUT modules:
INPUT 1 Word; INPUT 2 Words; ..................................; INPUT 9 Words
OUTPUT 1 Word; OUTPUT 2 Words; ..................................; OUTPUT 9 Words
Select one INPUT module and then one OUTPUT module to match the
GET
GET
FROM
FROM
s and
GOTO
GOTO
s
(respectively).
4.6.5 Acyclic Data
Parameters can be accessed acyclically from the PLC using DP-V1 read/write services.
Slot
= (parameter 254) / 255
Index
= (parameter 254) MOD 255
Size
= 2 (bytes)
For example:
409)SUMMER
409)SUMMER
1
1
INPUT
INPUT
2
2
is
Slot:Index:Size 2:153:2
4.6.6 Electronic Data Sheet
PROFIBUS gsd files:
plxjlx_1815.gsd
PLX or JLX
M40
plxjlx_M30_1811.gsd
PLX or JLX
M30