4.10 SWVER
This allows the software version to be viewed.
4.11 SEt PASS
This allows the default pass code to be changed
to a user defined value.
It is important that if the default pass code is
changed that the new value is noted and kept safe.
The new pass code can be recorded on the Table
in Section 9, page 50.
4.9.3 CONSt ALARM
This allows the constant flow alarm to be turned off.
The constant alarm is switched to on by the default factory setting. It detects if the flow has
been constant for long periods when at pressure, which may indicate a stuck cone due to
debris. If the system that the TVA is fitted to, has long periods where there is zero flow, but
the line is kept at a constant pressure, it is advisable to turn the alarm off to avoid unwanted
alarm messages.
ON
This enables the saturated steam alarm.
OFF
This disables the saturated steam alarm.
dELAy
This enables the time duration before alarm is displayed.
4.9.4 SAt ALARM
yES
Enables the Sub Saturation Alarm.
NO
Disables the Sub Saturation Alarm.
dELAy
This sets the time duration before alarm is displayed. Can be zero.
This allows the Sub Saturation Alarm to be enabled or disabled.
The Sub Saturation alarm is switched off by default. If set it will alarm if the steam temperature
drops 2 °C below saturation temperature.