12
3. Installation
Note: Before actioning any installation observe the 'Safety information' in Section 1.
To meet its specified accuracy and performance it is essential that the following installation
guidelines are followed carefully. For steam applications sound steam engineering practices
should be followed, including the use of separators. The installation must conform to all
relevant construction and electrical codes.
Fig. 5 Typical installation
TVA
flowmeter with
Superheat kit
fitted
Steam
Spool
piece
V3
V1
A bypass line will enable safe removal of the TVA flowmeter for maintenance or calibration.
Closing valves
V1
and
V2
and opening valve
V3
will allow the TVA flowmeter to be isolated
for re-zeroing (temperature to be <20
°C).
Trap set
Separator
Strainer
CAUTION:
If the electronic housing is mounted
at an angle of more than 45° from the
vertically downward position the PMO
(maximum operating pressure) must
be limited to 7 bar g (101 psi g) and
saturated steam applications only.
The electronic housing must be
mounted vertically downward for all
superheated applications.
Fig. 4 Installation limiting conditions
Limited to
7 bar g (101 psi g)
and
saturated steam
applications
only
For saturated steam
applications
over 7 bar g (101 psi g)
to 32 bar g (464 psi g) and all
superheated applications up to
23 bar g (333.5 psi g).
V2