Press
YES (F1)
ONLY
if you want to reset the CRC and generate a new
CRC value.
Simulation
This menu allows for the simulation of flow rate, temperature and flow
input voltage. It should only be used for testing and demonstration
purposes.
Make sure to return all of these simulation values to zero, before
returning to the normal mode of operation.
Note: Simulated values are only enabled when not set to zero.
Caution:
If the 4 to 20mA and/or the pulse outputs are connected to
controllers, set the controllers to “manual”. This will ensure that the
simulated signals do not cause false controller action.
The menu is accessible from the main programming menu by pressing
FLO
, and
DGN (F1)
:
F1 F2 F3 F4
Pressing
DGN (F1)
will show:
F1 F2 F3 F4
Pressing
SIM (F1)
will show:
F1 F2 F3 F4
Enter the value and then press
OK (F4)
.
FLOW PARAMETER 1
DGN UNT PRM EXIT
DIAGNOSTIC
SIM TST EXIT
FloSim = 0 SCFM
CHG OK
48
Operation: Programming
Programming
Using
the Local Display