To Program the Password:
Press
PSW (F2)
key to select password.
This screen displays the current
Level 1
password.
Press CHG (F1) key to change the password and enter new value (see
p. 28 for further details).
Press
OK (F4)
to accept new data and exit programming by pressing
EXIT (F4)
key repeatedly until out of the programming mode.
Note: Password can be number or letter characters up to 4 digits.
Units Settings
This menu is used to set the units for mass flow, temperature, pressure
reference and the settings of reference temperature, reference pressure
and density of gas when using Lbs/time or Kg/time.
These values will be set at Spirax Sarco, using the Application Data
Sheet values. If the customer changes the application, these values
can be changed to match the new application. Check with Spirax Sarco
Technical Support before changing the application gas.
The unit setting is accessed from the base programming menu by
pressing
FLO (F2)
:
PASSWD = 1234
CHG OK
FLOW PARAMETERS 1
DGN UNT PRM EXIT
SET PARAMETERS
I/O FLO DSP EXIT
39
Operation: Programming
Programming