Statutory regulations governing installation
Thermo E 200/320
34
5.3.4 Exhaust system
5.3.4.1
The exhaust outlet must be located so as to prevent emissions
from entering the vehicle through ventilators, heated air inlets or opening
windows.
5.3.5 Combustion air inlet
5.3.5.1
The air for the combustion chamber of the heater must not be
drawn from the passenger compartment of the vehicle.
5.3.5.2
The air inlet must be so positioned or guarded that blocking by
rubbish or luggage is unlikely.
5.3.6 Heating air inlet
not applicable
5.3.7 Heating air outlet
not applicable
5.3.8 Automatic control of the heating system
5.3.8.1
The heating system must be switched off automatically and the
supply of fuel must be stopped within five seconds when the vehicle’s
engine stops running. If a manual device is already activated, the
heating system can stay in operation.
ATTENTION!
Failure to follow the installation instructions and the notes contai-
ned therein will lead to all liability being refused by Spheros. The
same applies if repairs are carried out incorrectly or with the use of
parts other than genuine spare parts. This will result in the invali-
dation of the type approval for the heater and therefore of its
ECE
Type Approval
.
CAUTION!
At petrol stations and other fuel filling facilities the heater must be
switched off due to the explosion hazard. To advice to this require-
ment the self-adhesive label with the text ’’Switch off heater before
refueling!“, delivered with each heater, is to be affixed next to the
filler neck.