Manual for dialog Web
Order no.: 443 150
Presence
If the buttons of the operating module are not used to switch the energy
level and manual logon and logoff is enabled in the parameter
UCPTenableOcc, the logon or logoff telegram specified in UCPToccCmds is
sent on the nvoOccupancy when the corresponding button is selected.
Operating module "Fan control"
The operating module fan control offers functions for both value
acquisition and value output:
Value
Function
used interface components
fan
registration and
display
nviUnitStatus.fan_output,
nviSccSync.fan_output
setting
Parametrization:UCPTenableFan,
UCPTfanLevels
Output:
nvoFanSpeed ,
nvoSccSync.fan_output
supply air
registration and
display
nviSccSync.damper_output
setting
Parametrization:
UCPTenableFreshAir,
UCPTfreshAirOnCmd
Output:
nvoSccSync.damper_output
Fan
The fan is displayed and adjusted in stages, with evaluation of the
UCPTfan levels.
The values recorded from nviUnitStatus.fan_output and
nviSccSync.fan_output are evaluated for display.
If the setting of the fan level in the parameter UCPTenableFan is enabled,
it can be increased or decreased via the buttons.
Supply air
Display and setting of the supply air request is only possible using the
nviSccSync and nvoSccSync synchronisation interfaces.
The values received in nviSccSync.damper_output are displayed.
If a manual supply air request is enabled in the parameter
UCPTenableFreshAir, it can be triggered via the corresponding button. In
doing so, the output value specified in the parameter
UCPTfreshAirOnCmd is displayed on the nvoSccSync.damper_output.