Manual for dialog Web
Order no.: 443 150
Network output variables
nvoOccupancy
specification of the energy
level/room occupancy
status for individual room
controller
Type:
SNVT_occupancy
Value range:
level
value
Protection OC_NUL
Comf. OC_OCCUPIED
Comf.-ext. OC_BYPASS
Standby OC_STANDBY
Econ.
OC_UNOCCUPIED
Preallocation:
„Protection“ (OC_NUL)
Transmission:
once for button click
nvoFanSpeed
input for local setpoint shift
Type:
SNVT_switch
Value range:
depending on
UCPTfanLevels
.value with:
0 ... (1/n)*100%
stage 1
(1/n)*100%+1 … (2/n)*100% stage 2
((n-1)/n)*100%+1... 100% stage n
.state with:
0
Off
1
Off if .value = 0
On if .value > 0
-1
Automatic activated
Preallocation:
0.00°C (0)
Special feature: polled
nvoSetpt
Offset
local setpoint adjustment
Type:
SNVT_temp_p
Value range:
-10.00 ... + 10.00 °C
Preallocation:
0.00 °C (0)
Transmission:
once for button click
nvoSccSync
for output of the controller
statuses for
synchronisation with other
room climate control units
Type:
structure
(UNVT_scc_sync)
Transmission:
once for button click
Configuration parameter
UCPToperating
Location
local description of the
room to be operated (only
displayed on web
interface)
Type:
unsigned char[16]
(UCPT #88)
Value range:
String_ascii
Preallocation:
„Room x“
(x = index of the object)
UCPTsetptRange
maximum adjustment
range of the local setpoint
shift
Type:
structure
(UCPT #91)
Value range:
.min_range SNVT_temp_p
.max_range SNVT_temp_p
.step
SNVT_temp_p
Preallocation:
-3 K, +3 K, 0.5K (-300, 300,
50)
Version 2.01
Page 37 / 47
01.09.2020