Manual for dialog Web
Order no.: 443 150
Functional components - Room climate control
The function component room climate control is based on the
SFPTsccCommandModule function profile. It defines the function of the
"Energy level", "Room temperature" and "Fan control" control modules.
Interface components
Version 2.01
Page 34 / 47
01.09.2020
UFPTwebOperationPanel
UFPT #23203
UCPToperatingLocation
(UCPT #88
unsigned char[16])
UCPTstptRange
(UCPT #91
structure)
UCPTfanLevels
(UCPT #92
unsigned short)
UCPTfreshAirCmdOn
(UCPT #18
SNVT_lev_cont)
UPCThvacMode[4]
(UCPT #99
enumerated)
UCPToccCmds
(UCPT #90
structure)
UCPTenableFreshAir
(UCPT #51
boolean)
UCPTenableFan
(UCPT #93
boolean)
UCPTenableOcc
(UCPT #94
boolean)
UCPTenableHvacMode
(UCPT #103
boolean)
SCC Command Module
nviEnergyHoldOff
SNVT_switch
nvoSetptOffset
SNVT_temp_p
nviSpaceTemp
SNVT_temp_p
nvoOccupancy
SNVT_occupancy
nviUnitStatus
SNVT_hvac_status
nviEffectOcc
SNVT_occupancy
nviSetptOffsetFb
SNVT_temp_p
nvoFanSpeed
SNVT_switch
nviSccSync
UNVT_scc_sync
nvoSccSync
UNVT_scc_sync