Manual for dialog Web
Order no.: 443 150
Parametrierung des Funktionsobjektes
UCPTswitch
Use
operating module type
Type:
enumerated
(UCPT #97)
Value range:
-1 SU_NUL (invalid)
0 SU_LIGHT
_SWITCHED
1 SU_LIGHT_DIMMED
2 SU_SB_VENETIAN
3 SU_SB_SHUTTER
4 SU_WINDOW
Preallocation:
invalid {-1}
UCPTenable
Auto
specifies whether the
sending of "invalid"
values (undoing an
override) is permitted
Type:
boolean
(UCPT #98)
Value range:
0
BOOL_FALSE
1
BOOL_TRUE
Preallocation:
not allowed {0}
SCPTstep
Value
specifies the dimming
step size
Type:
SNVT_lev_cont
(UCPT #92)
Value range:
0,5 ... 100,0%
Preallocation:
5% {10}
UCPTslatAngle
Step
step angle for slat
adjustment
Type:
SNVT_angle_deg
(UCPT #3)
Value range:
- 90° ... +90°
Preallocation:
10° {500}
UCPTswitchOn
Value
value at 'switch on'.
Type:
SNVT_switch
(UCPT #21)
Value range:
SNVT_switch
Preallocation:
On with 100% {200, 1}
UCPTminOut
smallest value that may be
sent
Type:
SNVT_lev_cont
(UCPT #26)
Value range:
0,0 % ... 100,0 %
Preallocation:
Off at 0% {0}
SCPTmaxOut
upper threshold for
switching and dimming
processes
Type:
SNVT_lev_cont
(SCPT #93)
Value range:
0,0 ... 100,0%
Preallocation:
On with 100% {200}
UCPTswitch
Desc
text for object name
Type:
unsigned char[16]
(UCPT #19)
Value range:
string_ascii
Preallocation:
„Switch“
Version 2.01
Page 30 / 47