Miscellaneous
78
SafEye
TM
Xenon 700S Gas Detector User Guide
D.2.2
Alarm Operation Using the 0
–20mA Signal Current
The connected controller monitors the 0–20mA signal current for valid
values. (See
Mode
Normal
Warning
Alarm
Continuous current
with low sensitivity
(Full Scale: 5 LEL.m)
4mA/0 LEL.m
7.2mA/1
LEL.m
13.6mA/3
LEL.m
Continuous current
with high sensitivity
(Full Scale: 2 LEL.m)
4mA/0 LEL.m
7.2mA/0.4
LEL.m
12mA/1 LEL.m
Discrete current
4mA
14mA
19mA
The connected controller monitors the 0–20mA signal current for values
below 4mA and above 20mA.
D.2.3
Relay Outputs
Relay outputs don’t comply with SIL-2 requirements.
D.3
Miscellaneous
The complete functional performance of the gas detector should be checked
every 6 months (gas detection, fault detection, performance of the 0–20mA
signal current and the relays, gas alarms on and off).
The HART and RS-485 interfaces are not meant for the transmission of
safety related data.