This appendix details the special conditions for compliance with the
requirements of EN 61508 for SIL-2.
The SafEye 700S can be used in low and high demand mode applications,
see
IEC 61508.4, Chapter 3.5.12
.
D.1
Safety Relevant Parameters
Perform the following functional check of the detector every 6 months:
HFT: 0
PFD: 3.3 x 10
-4
(3.3% of SIL-2)
PFH: 1.5 x 10
-4
(15% of SIL-2) - For 0–20mA signal current application.
SFF: Fulfills the conditions of EN 61508 for SIL-2.
D.2
Guidelines for Configuration, Installation,
Operation, and Maintenance
Alarm conditions complying with SIL-2 can be implemented only with 0–
20mA outputs.
D.2.1
Conditions for Safe Operation
The SafEye 700S should consist only of the approved hardware and
software modules.
The 24C power supply must fulfill the requirements for “safe low voltage”
according to EN 60950 (PELV/SELV).
After installation and configuration the setup parameters must be
verified and the function of the SafEye 700S (gas detection, function of
the 0–20mA interface, relay functions) must be checked completely.