Detector Terminal Wiring
52
SafEye
TM
Xenon 700S Gas Detector User Guide
Detector Terminal Wiring
5.7
The detector has 3 output wiring options in the rear, segregated, “Exde”
terminal section, with 9 Terminals, labeled 1–9.
Option 3 is the default unless otherwise specified at the time of the order.
The following describes the function of each electrical terminal of the
detectors for all wiring options:
Table 18: Wiring Options
Wiring
Option
Terminal Number
1
2
3
4
5
6
7
8
9
3
(Default)
24VDC 0VDC Alarm
Relay
(1)
RS-485+
(3)
RS-485-
(3)
0–20mA
+
(4)
0–20mA -
(4)
RS-485
RTN
(6)
2
24VDC 0VDC Alarm
Relay
(1)
Fault Relay
(2)
Accessory Relay
(5)
not used
1
24VDC 0VDC Alarm
Relay
(1)
Fault Relay
(2)
0–20mA
+
(4)
0–20mA -
(4)
not used
Notes
:
The Alarm output is a N.O. contact relay (SPST).
The contacts are closed in gas alarm state.
The fault output is N.C. SPST relay. The contacts are closed when the
detector is in its normal operational condition.
Used for communications network as specified in
Configurations, page 67.
Configurations, page 67 for more details.
The accessory output is N.O. (SPST) relay. The accessory relay may
act in parallel with the alarm relay to activate another external
device or it may provide a warning signal, depending on the function
setup.
Used as RTN to the RS-485 Communications port.