– 35 –
Split Inverter Air-to-Water Heat Pump
Parameter List
Operation
Section Code Description
Units
Range
Default Notes
H
H01 EVI Operation
N/A
0 to 3
3
0 = EVI Inactive, 1 = EVI in Cooling, 2 = EVI in Heating, 3 = Both
H02 Running Mode
N/A
0/1
0
Manufacturer setting, do not alter
H03 Auxiliary Electic Heater
N/A
0/1
0
0 = No Aux Heater, 1 = Aux heater installed and active
H04 Heat Pump Mode
N/A
0 to 2
0
Manufacturer setting, do not alter
H05 Remote Enable & Heat Cool selection
N/A
0/1
0
0 = Console touchscreen operation, 1 = Wired remote operation
H06 Not Used
H07 Not Used
H08 Not Used
H09 Not Used
H10 Temperature Measurement Units
N/A
0/1
1
0 = Celsius, 1 = Farenheit
H11
DHW Operation
N/A
0/1
0
0 = DHW operation disabled, 1 = DHW operation enabled
H12 Not Used
H13 Not Used
P
P01
Pump Operation
N/A
0 to 2
0
0 = For Console Operation, 1 = For Wired Operation, 2 = Interval
P02
Interval Pump Off duration
Min.
1 to 120
10
If P01 = 2, Pump Starts every P02 minutes when no call is present
P03
Interval Pump On duration
Min.
1 to 30
3
If P01 = 2, Pump runs for P03 minutes, or until call is satisfied
P04
Not used
R
R01 Supply Temp target setpoint, Cooling
Deg F
R16 to 77
42
Cannot be less than the value of R16
R02 Supply Temp target setpoint, Heating
Deg F
77 to R15
120
Cannot be greater than the value of R15
R03 Difference from setpoint to Start Cooling
Deg F
0 to 18
6
Compressor starts in cooling when water temp rises to R01 + R03
R04 Difference from setpoint to End Cooling
Deg F
0 to 18
2
Compressor stops in cooling when water temp falls to R01 - R04
R05 Difference from setpoint to Start Heatling
Deg F
0 to 18
10
Compressor starts in Heat when water temp falls to R02 - R05
R06 Difference from setpoint to End Cooling
Deg F
0 to 18
4
Compressor starts in Heat when water temp rises to R02 + R06
R07 Difference fromsetpoint for Electric Heat
Deg F
0 to 18
4
Electric heaters enabled when water temp is below R02 - R07
R08 Ambient temp for Electric heat w/Delay
Deg F
-58 to 68
20
Electric heaters available after delay when ambient is below R8
R09 Time Delay duration
Min.
0 to 120
10
Time delay in minutes for activiation of Electric Heaters
R10 Ambient Temp for Electric heat w/o Delay
Deg F
-58 to 68
-5
Electric heaters available immediately when ambient is below R10
R11
DHW Temp Setpoint
Deg F
95 to 131
125
Target setpoint of DHW Tank when enabled
R12 DHW differential to Start
Deg F
0 to 18
10
DHW Starts when Tank temp falls to R11 - R12
R13 DHW differential to End
Deg F
0 to 18
4
DHW Stops when Tank temp rises to R11 + R13
R14 Not used
R15 Maximum Heating Setpoint
Deg F
113 to 158
140
R02 Cannot be set greater than this value
R16 Minimum Cooling Setpoint
Deg F
35.6 to 53.6
36
R01 Cannot be set lower than this value
U
U01 Not used
U02 Not used
U03 Not used