Split Inverter Air-to-Water Heat Pump
5. Factory
Settings
From the home screen:
To adjust or view factory settings, press the "search" key once for 3 seconds, then again for another 3 seconds to enter the Password screen.
The password screen will display "000". Use the up or down arrows to enter password "066". Press the "M" key to accept the password.
The parameter list will begin with Section "A". Use the up or down keys to access the appropriate section based on the chart below. Once
the appropriate section is found, press the "M" key to access that sections parameter. For example: If contractor would like to change
the temp set-point in heating; Use the up and down to keys to enter a password of "066", press "M" to save the password, then use the
up or down keys to locate the section of "R" parameters and press "M". Once selected scroll to "R02" and press "M" again to access the
heating temp set-point parameter. Once the parameter has been adjusted, the contractor will press "M" to save. If "M" is not pressed,
parameter change will not be saved.
Parameter List
Operation
Section Code Description
Units
Range
Default Notes
A
A01
Minimum Operating Ambient Temp.
Deg F
-58 to 50
-22
Unit will not operate below this outdoor temperature
C
C01 Fixed Compressor Speed
Hz
0 to 120
0
A value of 0 results in modulating variable speed
C02 Minimum Compressor Speed
Hz
20 to 60
60
Lower end of modulation range
C03 Maximum Compressor Speed
Hz
30 to 120
90
Upper end of modulation range
C04 Compressor Model
N/A
-
-
Manufacturer setting, do not alter
D
D01 Min. Time between Defrost Cycles
Min.
5 to 90
45
Defrost cycle will not repeat sooner than this
D02 Max. duration of a Defrost Cycle
Min.
1 to 20
8
Defrost cycle will not run longer than this
D03 Coil Temp to Exit Defrost
Deg F
1.8 to 86
45
Defrost cycle will end when coil reaches this temp
D04 Fixed Coil Temp to Start Defrost
Deg F
-58 to 32
19.4
If Defrost Reset is NOT selected
D05 Min. Coil Temp to start Defrost
Deg F
-58 to 5
-22
Lower end of Defrost Reset Curve, Coil Temp
D06 Ambient Temp Spread of Defrost Curve
Deg F
33.8 to 86
33.8
Ambient temp range below 35.6°F of Defrost curve
D07 Coil Temp Spread of Defrost Curve
Deg F
32 to 86
32
Coil temp range above D05, of Defrost Curve
D08 Not used
D09 Enable Defrost Reset
N/A
0/1
1
0 = Fixed Defrost per D04, 1 = Defrost Reset per D05, D06 & D07
D10 Aux Electric Heat during Defrost
N/A
0/1
0
0 = No Aux Heat during Defrost, 1=Aux Heat during Defrost
D11
Compressor Speed during Defrost
Hz
30 to 90
70
Fixed compressor speed during Defrost only
E
E01
EEV Mode
N/A
1
1
Manufacturer setting, do not alter
E02
EEV Superheat in Heating operation
Deg F
-18 to 18
1.8
Manufacturer setting, do not alter
E03
EEV initial opening at startup in Heating
Steps
0 to 480
0
Manufacturer setting, do not alter
E04
EEV Superheat in Cooling operation
Deg F
-18 to 18
7.2
Manufacturer setting, do not alter
E05
EEV initial opening at startup in Heating
Steps
0 to 480
350
Manufacturer setting, do not alter
E06
EEV Minumum opening during operation
Steps
0 to 480
100
Manufacturer setting, do not alter
E07
EEV Opening during Defrost operation
Steps
0 to 480
480
Manufacturer setting, do not alter
E08
EVI EEV Mode
N/A
0/1
1
Manufacturer setting, do not alter
E09
EVI EEV Superheat
Deg F
-18 to 18
1.8
Manufacturer setting, do not alter
E10
EVI EEV initial opening
Steps
0 to 480
150
Manufacturer setting, do not alter
E11
EVI EEV Minumum opening during opn
Steps
0 to 480
100
Manufacturer setting, do not alter
F01
Fan Mode
N/A
0/1
1
Manufacturer setting, do not alter
F02
Fan Quantity
N/A
0/1
0
Manufacturer setting, do not alter
F
F03
Fixed Fan Speed
RPM
0 to 1,000
0
A value of 0 results in modulating variable speed
F04
Max fan speed in Heating Mode
RPM
0 to 1,000
700
Upper end of modulation range
F05
Min fan speed in Heating Mode
RPM
0 to 1,000
200
Lower end of modulation range
F06
Coil Temp for Max Fan Speed, Heating
Deg F
-10 to 104
5
Coil temp at Upper end of fan speed range
F07
Coil Temp for Min Fan Speed, Heating
Deg F
-10 to 104
36
Coil temp at Lower end of fan speed range
F08
Max fan speed in Cooling Mode
RPM
0 to 1,000
700
Upper end of modulation range
F09
Min fan speed in Cooling Mode
RPM
0 to 1,000
200
Lower end of modulation range
F10
Coil Temp for Max Fan Speed, Cooling
Deg F
-10 to 104
105
Coil temp at Upper end of fan speed range
F11
Coil Temp for Min Fan Speed, Cooling
Deg F
-10 to 104
80
Coil temp at Lower end of fan speed range