27
Generator Autostart wiring (optional)
There are 3 methods for wiring the autostart
circuit, based on the requirements of the
generator used:
1. 12V
2. 24V
3. Dry Contact (Continuity)
The sonnenBatterie ecoLinx storage system has
ports for all three methods.
12V Signal
1. Locate the green, 2-position plug connector
provided in the accessory kit.
2. Insert stripped ends of customer’s 12V
connection cables into the 2-position plug.
3. Ensure the positive cable is on the bottom
and the negative cable is on the top.
4. Insert the plug into the J11 port on the HUB
board as shown in
Fig. 32
below.
Fig. 32 12V signal connection
24V Signal
1. Locate the green, 2-position plug connector
provided in the accessory kit.
2. Insert stripped ends of customer’s 24V
connection cables into the 2-position plug.
3. Ensure the positive cable is on the bottom
and the negative cable is on the top.
4. Insert the plug into the J12 port on the HUB
board as shown in
Fig. 33
below.
Fig. 33 24V signal connection
Dry Contact
1. Ensure that the 2-pin jumper at the top of
the hub board is on jumper 2.
2. Locate the green, 3-position plug connector
provided in the accessory kit.
3. Insert stripped ends of customer’s dry
contact connection cables into the
3-position plug.
4. Ensure the dry contact connection cables
are located on the top two pins of the
3-position plug.
5. Insert the plug into the J13 port on the HUB
Summary of Contents for sonnenBatterie ecoLinx 10
Page 2: ......
Page 4: ......
Page 8: ......
Page 17: ...9 Dimensions Fig 1 Storage system dimensions Key components Fig 2 ecoLinx key components...
Page 30: ...22 page 23 page 23 page 29 page 23 Fig 22 Terminal map for ecoLinx...
Page 53: ...45 Appendix 1 Nameplates...
Page 54: ...46...
Page 55: ...47...
Page 61: ...53...
Page 62: ......
Page 63: ......