16
Inspecting the storage system
▶
Inspect the system.
▶
If there is any suspected damage or loose parts,
stop installation, photograph the affected area,
and contact sonnen's service department.
Mounting the storage system
WARNING
Risk of injury lifting the storage
system!
The storage system is heavy.
▶
Wear safety boots.
▶
Ensure you have stable footing.
▶
Mount the storage system in an
upright position.
Two people are required to mount
the storage system.
CAUTION
Risk of injury, cabinet may fall
over!
Until the battery modules
are installed, the cabinets are
extremely top-heavy.
▶
Hold onto the storage system
during installation.
1. Install the mounting cleat
Tools needed:
‒
Powered drill
‒
3/16” bit
▶
Drill two holes into studs in the desired location
with a 3/16” drill bit 16 inches on center.
Furr out the wall as necessary. Secure the
mounting cleat to the wall with at least two
5/16" lag screws driven to at least two inches of
penetration. Center the screws at the following
heights:
• With small battery extension cabinet: 68 5/16”
• With large battery extension cabinet: 76”
Fig. 9 Mounting cleat orientation