ID
Option
Description
1
off (default)
IOUT2 is inactive.
2
value, tem-
perature
The air temperature is returned.
3
status, level
limit
If the level exceeds the limit specified in
, 20 mA is applied, oth-
erwise 0 mA.
4
status, snow
settling
If the USH-9 detects a snow cover 20 mA is applied, otherwise 0 mA. A
snow cover is detected if
exceeds the spe-
cified limit and
is not reached.
5
status, snow-
fall
If the USH-9 detects snowfall 20 mA is applied, otherwise 0 mA. Snowfall
is detected if
is exceeded and the tem-
perature is below
6
status, all lim-
its
If any limit mentioned above is violated, 20 mA is applied, otherwise
0 mA.
D-F-F
IOUT2, temperature 4-20 mA span
ush-iout2-temperature-span
Defines the output range of the 4-20 mA signal of IOUT2 . The span should cover the air temperature
range expected at the measurement site.
Value range
Default
Units
-9ˈ999ˈ999…99ˈ999ˈ999
100
Unit of temperature
D-F-G
IOUT2, temperature 4 mA value
ush-iout2-temperature-4ma-value
Defines the minimum air temperature that corresponds to the 4 mA current output.
Value range
Default
Units
-9ˈ999ˈ999…99ˈ999ˈ999
-40
Unit of temperature
D-F-H
IOUT2, status hold time
ush-iout2-status-hold-time
1
4
P
ar
am
et
er
d
ef
in
it
io
n
s
108