CB 230 RTS
Reflex photoelectric cell
•
Wiring to "Cell active during closing input" with autotest - Fig. 15
230V orange light - Fig. 16
Orange light warning (2 s before the gate starts moving) activated via dipswitch 11.
aerial - Fig. 17
12Vac electric lock (Ref. 9019552) - Fig. 18
The power supply for the electric lock is not provided by the control box.
keyswitch - Fig. 19
Video doorphones - Fig. 20
7 - aDVanCED PaRaMEtER SEttIng
The change in dipswitch status is taken into account immediately.
By default, all dipswitches are OFF.
7.1 torques for motors 1 and 2 - Dipswitches 1 to 4
Motor 1 torque
setting
DIP - SW 1
DIP - SW 2
Setting
oFF
oFF
100% torque
OFF
ON
75% torque
ON
OFF
50% torque
ON
ON
25% torque
Motor 2 torque
setting
DIP - SW 3
DIP - SW 4
Setting
oFF
oFF
100% torque
OFF
ON
75% torque
ON
OFF
50% torque
ON
ON
25% torque
7.2 gate leaf mode 1 - Dipswitch 5
DIP - SW 5
Setting
oFF
Both motors operating
ON
One motor only operating
Power is not supplied to the output M2.
All operating modes cane be used.
7.3 offset of the gate leaves during closing - Dipswitch 6
DIP - SW 6
Setting
oFF
Offset during closing identical to the offset during
opening, set during programming
ON
Offset during closure of 20 s
7.4 operating modes - Dipswitches 7 to 9
DIP -
SW 7
DIP -
SW 8
DIP -
SW 9 Setting
Sequential
oFF oFF oFF
Each press on the remote control button causes the
motor to move (initial position: gate closed) as per
the following cycle: open, stop, close, stop, open,
etc.
Sequ automatic timed close
OFF OFF ON
Operation in automatic closing mode is only
authorised if the photoelectric cells are fitted.
In sequential mode with automatic timed close:
- the gate closes automatically after the time delay
programmed with the
tIME
potentiometer,
- pressing a button on the remote control interrupts
the movement taking place and the timed close
(the gate remains open).
Semi-automatic
OFF ON
OFF In semi-automatic mode, the gate is always closed
or open:
- pressing a button on the remote control during
opening has no effect,
- pressing a button on the remote control during closing
causes it to reopen.
automatic
OFF ON
ON
In automatic mode, the final position of the gate will
always be the closed position.
Operation in automatic closing mode is only
authorised if the photoelectric cells are fitted.
- the gate closes automatically after the time delay
programmed with the
tIME
potentiometer,
- pressing a button on the remote control during
opening has no effect,
- pressing a button on the remote control during
closing causes it to reopen,
- pressing a button on the remote control during the
closing time delay restarts the time delay (the gate will
close when the new time delay has elapsed).
If there is an obstacle in the cells' detection zone,
the gate will not close. It will close once the obstacle
is removed.
aut cell blocking
ON
OFF OFF
In automatic mode, the final position of the gate will
always be the closed position.
Operation in automatic closing mode is only
authorised if the photoelectric cells are fitted.
After the gate is opened, movement in front of the
cells (if active cell input during closing is activated)
will close the gate after a short time delay (fixed at
2 seconds).
If there is no movement in front of the cells, the
gate will close automatically after the timed close
programmed in with the
tIME
potentiometer.
If there is an obstacle in the cells' detection zone,
the gate will not close. It will close once the obstacle
is removed.
Deadman's wired control
ON
ON
ON
The gate can only be controlled by continuous action
on a wired control: opening on OPENING control
input, closing on CLOSURE control input,
The pedestrian and radio controls are inactive.
There is no slowdown zone when the deadman's
wired control is operating,
This operating mode can be activated without
programming.
7.5 lock release - Dipswitch 10
DIP - SW 10
Setting
oFF
Without lock release
ON
With lock release: before opening, the motors give a
gentle push in the closing direction.
7.6 orange light warning - Dipswitch 11
DIP - SW 11
Setting
oFF
Without warning
ON
With 2 s warning prior to movement
7.7 Cell autotest when closing - Dipswitch 12
DIP - SW 12
Setting
oFF
Without autotest
ON
With autotest: the autotest is only available for the cell
connected to the cell active during closing input.