Project  Slidetronic  II  solves  control  of  magnets  (brakes)  of  fire  gates.  Power  of  control 

circuits can be backed up by an additional battery module, which can keep gate in open 
position in case of power failure. 

3.

 

INSTALLATION AND SETUP 

Before the initial startup, mechanical part of gate installation has to be fully completed to 

avoid mechanical damage of the gate during magnet/brake release. 
Before first activation connect only: 

power cable 

cable of magnet/brake 

terminals EPS (10 and 11) NC contact (during the contact disconnection, the panel is in 
alarm) 

if  Slidetronic  II  is  equipped  with  a  battery  module,  connect the battery  to  control 

panel,  the  battery  is  delivered  in  disconnected  status  –  there  is  an  insulator 
between the battery contact, which has to be removed (see the Picture 2: Battery 
Module) 

check if the resistance 4.7 kΩ is connected to the terminals 1, 2 (if the resistance is 
not connected, the panel is  in alarm) 

Control  panel  Slidetronic  II  is  standardly  equipped  with  a  keyboard  with  "Start  /  Stop" 

buttons and also "Reset" button, which causes reset of the panel in case of alarm raised 
by local sensors. Gate can be stopped by the STOP button at any time. 
When  opening  the  control  panel,  be  careful  to  avoid  damage  of  printed  cable  placed 
between the keyboard and PCB. 

When you activate the EPS – contact between 10 and 11 is disconnected and panel is in 
alarm. In case of connection of the contacts, the panel is automatically in standby mode. 
In case of power failure, voltage is kept approximately 1 hour and then the power supply is 

disconnected in 8, 9 and the panel goes into standby mode. 
IF  ANY  FUSES  IN  THE  SWITCHBOARD  ARE  BLOWN,  THEY  CAN  BE  REPLACED 
ONLY  ONCE.  IF  THEY  ARE  BLOWN  AGAIN,  THEIR  REPLACEMENT  IS  NOT 

PERMITTED. 
IF  THE  PROCEDURE  STATED  IN  THE  TECHNICAL  DOCUMENTATION  IS NOT 
RESPECTED, IT MAY LEAD TO THE LOSS OF WARRANTY. 
IN THE EVENT OF MALFUNCTION, AT FIRST, IT IS NECESSARY TO DETECT THE 

POSSIBLE  CAUSE  OF  THE  MALFUNCTION  AND  REPAIR  IT.  AFTER  THE 
MALFUNCTION IS REPAIRED, IT IS POSSIBLE TO REPLACE THE BLOWN FUSE. 
IT  IS  FORBIDDEN  TO  MANIPULATE  WITH  THE  CIRCUITS  OF  THE 

SWITCHBOARD  AND  CHANGE  THEIR  CONNECTIONS.  IF  THIS  CONDITION  IS 
NOT  COMPLIED,  IT  IS  NO  LONGER  POSSIBLE  TO  APPLY  THE  SWITCHBOARD 
WARRANTY.  
THE  SWITCHBOARD  CANNOT  BE  OPENED  BY  A  PERSON  WITHOUT AN 
APPROPRIATE  TRAINING  AND  QUALIFICATION  ACCORDING  TO  THE  DECREE 
NO. 50/1978, § 6. 

Summary of Contents for SLIDETRONIC II

Page 1: ...sko IČ 29260159 DIČ CZ29260159 tel 420 547 427 011 www somati system cz 02 2017 CONTROL PANEL SLIDETRONIC II Producer Somati system s r o Jihlavská 510 2c 664 41 Troubsko okr Brno venkov Tel 547 427 011 Fax 547 427 013 E mail export somati system cz www somati system cz ...

Page 2: ...RONIC II 1 2 CONFIGURATION 2 3 INSTALLATION AND SETUP 2 4 FUNCTIONS OF THE CONTROL PANEL SLIDETRONIC ii 3 5 DESCRIPTION OF INTERNAL TERMINAL 4 6 DESCRIPTION OF SETTINGS OF DIP SWITCH FUNCTIONS 4 7 DESCRIPTION OF FUNCTION WITH INDIVIDUAL SYSTEMS OF GATES SOMATI SYSTEM 6 8 RECOMMENDED EXTERNAL DEVICES 7 9 ELECTRICAL AND DIMENSION DATA 7 10 DIAGRAMS 8 11 DECLARATION OF CONFORMITY 9 ...

Page 3: ...IČ CZ29260159 tel 420 547 427 011 www somati system cz 1 Primarily designed to control gravitational fire closures produced by Somati system s r o The panel can be also used to control hinged fire closures together with electromagnetic anchors and closers 1 CONTROL PANEL SLIDETRONIC II ...

Page 4: ...h Start Stop buttons and also Reset button which causes reset of the panel in case of alarm raised by local sensors Gate can be stopped by the STOP button at any time When opening the control panel be careful to avoid damage of printed cable placed between the keyboard and PCB When you activate the EPS contact between 10 and 11 is disconnected and panel is in alarm In case of connection of the con...

Page 5: ...voltage 230 V On network is connected Flashing no network if the battery is connected Off stopped activity no voltage 230 V and no battery LED red LED movement of gate On gate is not moving Flashing gate is closing LED yellow LED battery status On charged over 3 9 V Flashing battery is charging Off discharged or no battery LED red LED error 1 flash alarm of detectors 2 flash alarm of EPS If the tw...

Page 6: ...T2 0 130 s OFF brake release has no time limit DIP 3 ON time of brake activation is set by trimmer T2x3 0 390 s DIP 3 is valid for new devices from 2015 older devices are without the function OFF brake activation has no time limit DIP 4 no function Trimmer T1 time of pre flashing 0 13 s from program version V2 3 it is 0 51 s After pressing the START button siren is activated at first and after pas...

Page 7: ...then is released again After returning from alarm EPS activates the brake and after the time 3 x T2 it also releases the brake After pressing keyboard button or external button for release brake is released permanently if DIP2 is OFF in case DIP2 is ON brake is released for T2 then is activated for time 3 x T2 and after that is released permanently Changes are valid for devices from 2015 which has...

Page 8: ... position due to the magnet When opening the fire closure please take extra care to avoid mechanical damage of the magnet and its function especially when the gate is almost closed to the end position max opening it is necessary to reduce the speed of closing to minimize the impact on the electromagnet B System of electromagnetic brake In case of fire the central unit of fire alarm system or local...

Page 9: ...s to be kept otherwise the fuse on the module is interrupted Time of the backup function of the battery fully charged and in good condition is about 1 hour assuming own consumption and usage of brake 24 V 0 1 A or warning light 24 V 0 08 A New battery can reach 2 hours Fully charged battery requires approx 10 hours of charging 9 ELECTRICAL AND DIMENSION DATA Voltage 230 V 50 Hz Power input 10 VA O...