7.

 

DESCRIPTION  OF  FUNCTION  WITH  INDIVIDUAL  SYSTEMS  OF 

GATES SOMATI SYSTEM 

A.

 

System of electromagnet  
In case of fire, the central unit of fire alarm system or local detectors send a signal into 
the control panel which releases electromagnet holding the gate in open position. After 
the magnet is released the gate is closed gravitationally (using an inclined rail). After 

alarm  of  local  detectors  and  the  reactivation  of  the  system,  it  is  necessary  to  RESET 
the control panel (Figure 1: Control Panel) pressing the RESET button. If there is not 
installed a backup power, the gate also closes in case of power failure. During normal 

operation,  the  leaf  can  be  opened  manually  with  recessed  handles  and  closed  by 
pressing  START-STOP  buttons  on  the  control  panel  (Picture  1:  Control  Panel).  By 
pressing the START-STOP buttons once again, the voltage 24V on magnet is restored 
and gate stays in open position (due to the magnet). When opening the fire closure, 

please, take extra care to avoid mechanical damage of the magnet and its function – 
especially,  when  the  gate  is  almost  closed  to  the  end  position  (max.  opening),  it  is 
necessary  to  reduce  the  speed  of  closing  (to  minimize  the  impact  on  the 

electromagnet). 

B.

 

System of electromagnetic brake: 

In case of fire, the central unit of fire alarm system or local detectors send a signal 

into the control panel which releases electromagnetic brake holding the gate in open 
position. After the el. brake is released the gate is closed using counterweight system. 
After alarm of local detectors and the reactivation of the system, it is necessary to RESET 
the control panel (Figure 1: Control Panel) pressing the RESET button. If there is not 

installed a backup power, the gate also closes in case of power failure. During normal 
operation,  the  leaf  can  be  opened  manually  with  recessed  handles  and  closed  by 
pressing  START-STOP  buttons  on  the  control  panel  (Picture  1:  Control  Panel).  By 

pressing the START-STOP buttons once again, the gate stops. The advantage of the 
system  is  that  it  enables  to  stop  the  gate  in  any  position  and  also  to  regulate  the 
closing speed directly on electromagnetic brake. 

Summary of Contents for SLIDETRONIC II

Page 1: ...sko IČ 29260159 DIČ CZ29260159 tel 420 547 427 011 www somati system cz 02 2017 CONTROL PANEL SLIDETRONIC II Producer Somati system s r o Jihlavská 510 2c 664 41 Troubsko okr Brno venkov Tel 547 427 011 Fax 547 427 013 E mail export somati system cz www somati system cz ...

Page 2: ...RONIC II 1 2 CONFIGURATION 2 3 INSTALLATION AND SETUP 2 4 FUNCTIONS OF THE CONTROL PANEL SLIDETRONIC ii 3 5 DESCRIPTION OF INTERNAL TERMINAL 4 6 DESCRIPTION OF SETTINGS OF DIP SWITCH FUNCTIONS 4 7 DESCRIPTION OF FUNCTION WITH INDIVIDUAL SYSTEMS OF GATES SOMATI SYSTEM 6 8 RECOMMENDED EXTERNAL DEVICES 7 9 ELECTRICAL AND DIMENSION DATA 7 10 DIAGRAMS 8 11 DECLARATION OF CONFORMITY 9 ...

Page 3: ...IČ CZ29260159 tel 420 547 427 011 www somati system cz 1 Primarily designed to control gravitational fire closures produced by Somati system s r o The panel can be also used to control hinged fire closures together with electromagnetic anchors and closers 1 CONTROL PANEL SLIDETRONIC II ...

Page 4: ...h Start Stop buttons and also Reset button which causes reset of the panel in case of alarm raised by local sensors Gate can be stopped by the STOP button at any time When opening the control panel be careful to avoid damage of printed cable placed between the keyboard and PCB When you activate the EPS contact between 10 and 11 is disconnected and panel is in alarm In case of connection of the con...

Page 5: ...voltage 230 V On network is connected Flashing no network if the battery is connected Off stopped activity no voltage 230 V and no battery LED red LED movement of gate On gate is not moving Flashing gate is closing LED yellow LED battery status On charged over 3 9 V Flashing battery is charging Off discharged or no battery LED red LED error 1 flash alarm of detectors 2 flash alarm of EPS If the tw...

Page 6: ...T2 0 130 s OFF brake release has no time limit DIP 3 ON time of brake activation is set by trimmer T2x3 0 390 s DIP 3 is valid for new devices from 2015 older devices are without the function OFF brake activation has no time limit DIP 4 no function Trimmer T1 time of pre flashing 0 13 s from program version V2 3 it is 0 51 s After pressing the START button siren is activated at first and after pas...

Page 7: ...then is released again After returning from alarm EPS activates the brake and after the time 3 x T2 it also releases the brake After pressing keyboard button or external button for release brake is released permanently if DIP2 is OFF in case DIP2 is ON brake is released for T2 then is activated for time 3 x T2 and after that is released permanently Changes are valid for devices from 2015 which has...

Page 8: ... position due to the magnet When opening the fire closure please take extra care to avoid mechanical damage of the magnet and its function especially when the gate is almost closed to the end position max opening it is necessary to reduce the speed of closing to minimize the impact on the electromagnet B System of electromagnetic brake In case of fire the central unit of fire alarm system or local...

Page 9: ...s to be kept otherwise the fuse on the module is interrupted Time of the backup function of the battery fully charged and in good condition is about 1 hour assuming own consumption and usage of brake 24 V 0 1 A or warning light 24 V 0 08 A New battery can reach 2 hours Fully charged battery requires approx 10 hours of charging 9 ELECTRICAL AND DIMENSION DATA Voltage 230 V 50 Hz Power input 10 VA O...

Page 10: ...1 Troubsko IČ 29260159 DIČ CZ29260159 tel 420 547 427 011 www somati system cz 8 10 DIAGRAMS 2 types of detector slots D H or B401R 2 2 1 1 DETECTOR SLOTS Cable installation to the control panel Installation of the Battery Module Complete connections connections ...

Page 11: ...Platné od 7 3 2017 Somati system s r o Jihlavská 510 2c 664 41 Troubsko IČ 29260159 DIČ CZ29260159 tel 420 547 427 011 www somati system cz 9 11 DECLARATION OF CONFORMITY ...

Reviews: