DESCRIPTION OF INTERNAL TERMINAL
Input side:
1 – detectors 0 V – closed 4,7 kΩ loop for connection of
detectors between 1 and 2
2 – det24 V – closed 4,7 kΩ loop for connection of
detectors between 1 and 2
10,11 – EPS – potential-free contact NC
11,12 – START/STOP potential-free buttons – NO contact (external button)
Output side:
3 – COM
4 – NO
5 – NC
6 – warning light +24 V
7 – warning light 0 V
8 – brake/24 V
9 – brake/magnet 0 V
6.
DESCRIPTION OF SETTINGS OF DIP SWITCH FUNCTIONS
Controls:
DIP 1
output for warning light
ON = flashing only during alarm
OFF = flashing always when movement is detected
DIP 2
ON = time of brake release is set by trimmer T2 0–130 s.
OFF = brake release has no time limit
DIP 3
ON = time of brake activation is set by trimmer T2x3 = 0-390 s. (DIP 3 is
valid for new devices from 2015, older devices are without the function)
OFF = brake activation has no time limit
DIP 4
no function
Trimmer
T1
time of pre-flashing 0-13 s. (from program version V2.3 it is 0-51 s.)
After pressing the START button, siren is activated at first and after passage of the set
time, the gate starts closing.
Trimmer
T2
time of release 0 – 130 s.
It is an adjustable time during which, after pressing START button, the brake is released.
After passage of the set time the brake is activated again (by recovery of voltage in
terminals 8, 9). Time T2 is normally set the way that after complete closure of gate,
release of brake lasts another 10 seconds and then is activated again.
By setting of time T2 there is automatically set time of brake activation on triple value of
brake release (in case DIP 3 = ON).
output relay max. 60 V/3 A
max. 0,1 A
max. 0,1 A