73 • Control Keypad
_______________________________________________________________________________________________
7.8.7
I/O Programming Parameters – Page 6
I/O PROGRAMMING
PARAMETERS
Displays in MAXIMIZED MODE only
(refer to section
6.4.1 page 40 for changing mode)
Display and Default
Values
Range Description
PROG. INPUT # 7
RESET
RESET/
TEST/ MULTI SOFT
STOP (optional)
Sets terminal 7 function
Refer to section
7.8.7.1 on page 74.
PROG. INPUT # 8
DUAL ADJUSTMENT
DUAL ADJUSTMENT/
RESET
Sets terminal 8 function
Refer to section
7.8.7.1 on page 74.
FAULT RELAY TYPE
FAULT
FAULT/
FAULT – FAIL SAFE
Sets FAULT RELAY mode of operation.
When configured to FAULT the internal relay is
energized upon fault.
When configured to FAULT FAIL SAFE the relay is
de
-energized upon fault. In this mode, while normal
operation, the contacts are open.
Relay will also
de
-energize upon control power
outage.
IMM. RELAY TYPE
IMMEDIATE
IMMEDIATE/
# STRTS PREALARM
Sets IMM/ # STRT PREAL mode of operation.
When configured to IMMEDIATE the relay is energizes
at the start signal after the programmed RELAY ON
DELAY time has elapsed. It de-energizes at the end of
the deceleration time (if any) after the programmed
RELAY OFF DELAY time has elapsed.
When configured to # STRTS PREALARM the relay is
energized if a start command will cause the soft
starter to trip on TOO MANY STARTS.
RELAY ON DELAY
0 SEC.
0 – 3600SEC.
Sets IMM/ # STRT PREAL on delay time.
Sets IMM/ # STRT PREAL off delay time
RELAY OFF DELAY
0 SEC.
0 – 3600SEC.
ANALOG OUTPUT
RELATIVE CURRENT
RELATIVE
CURRENT/
RELATIVE POWER
When set to RELATIVE CURRENT the full scale of the
optional analog PCB output is related to 200% of
FLA
(2x<
Motor rated current
>).
Or, when set to RELATIVE POWER the full scale of
the analog PCB output is related to 200% of motor
power (2x<
Motor rated power
>).
Motor rated power is set in the MAIN & PROTECT
parameter. Refer to section
7.8.2 page 55.
STORE ENABLE
I/O PROG. PARAM.
Same as STORE ENABLE MAIN & PROTECT page
57.