161 • HRVS-DN Communication (Profibus protocol)
_______________________________________________________________________________________________
17.8
Number of Setting Registers for Data Request
17.8.1
Main & protect. parameters
Parameter
#
Range
Default
Rated
Line
Voltage 0 2300..15000
6600
(Volt.)
Starter FLC
1
20..1800
150 (Amp.)
Motor FLA
2
20..1800
150 (Amp.)
Rated Motor Power
3
50..40000
1000 (KW)
Service Factor
4
100..130 (% of FLA)
100 (%)
Undercurrent Trip
5
0..90
0 (% of FLA)
Undercurrent Delay
6
1..40
10 (Seconds)
Overcurrent Shear Pin
7
100..850
850 (% of FLA)
Overcurrent Delay
8
0..50
5 (0.5 Sec.)
Overload Class
9
IEC 5,10,15,20,25,30
NEMA 5,10,15,20,25,30 FLA)
IEC Class 10
Overload Protect
10
0=Disable
1=Enable While Run
2=Enable
1=Enable While Run
Unbalance Trip
11
10..100, 101 = Off
20 (%)
Unbalance Delay
12
1..60
5 (Seconds)
Ground Fault Trip
13
10..100, 101 = Off
20 (% of FLA)
Ground Fault Delay
14
1..60
5 (Seconds)
Undervoltage Trip
15
50..90
70 (%)
Undervoltage Delay
16
1..100
5 (Seconds)
Overvoltage Trip
17
110..125
120 (%)
Overvoltage Delay
18
1..10
2 (Seconds)
Reserved 20..24
17.9
Start Parameters
Parameter
#
Range
Default
Soft_Start_Curve 24
0..11 (6..11 are for Tacho
only)
1 (Standard).
Pulse Level
25
70 (%of FLA) – 700 (%of FLA) 70% of FLA
Pulse Time
26
0..10 (Tenth Seconds)
0 (No Pulse)
Initial Voltage /
Initial Current
27
10..80 /
100..400 % (of FLA)
30 (% of full voltage) /
100 (% of FLA)
Current Limit
28
100..700
400 (% of FLA)
Acceleration Time
29
1..90
10 (Seconds)
Max. Start Time
30
1..250
30 (Seconds)
Number Of Starts
31
1..10 & (11 = off)
1
Starts_Period 32
1..60
20
(Minutes)
Start Inhibit
33
1..60 minutes
15 (Minutes)
Run Contact Delay /
Turn Bypass On at
34
0..120 seconds /
121..250 % of Motor FLA
5 (Seconds) /
Only with relay card for
optional sync motor start
Min Time To Bypass
35 3..60
3 Sec
Only with relay card for
optional sync motor start
Reserved
36..39