149 • HRVS-DN Communication (Profibus protocol)
_______________________________________________________________________________________________
17.
HRVS-DN COMMUNICATION (PROFIBUS PROTOCOL)
17.1
Global Parameters:
33:
;=============================================
34:
;==== General DP Keywords ====================
35:
;=============================================
36:
37:
GSD_Revision = 5
38:
Vendor_Name = "Solcon Ltd"
39:
Model_Name = "HRVS-DN"
40:
Revision = "1.00"
41:
Ident_Number = 0x0BAB
42:
Protocol_Ident = 0
43:
Station_Type = 0
44:
FMS_supp = 0
45:
Hardware_Release = "V1.00"
46:
Software_Release = "V1.00"
47:
Redundancy = 0
48:
Repeater_Ctrl_Sig = 2
49:
24V_Pins = 0
Code 1 – Global Parameters in the GSD file
17.2
Operation Mode in PROFIBUS:
HRVS-DN supports both DPV0 and DPV1.
DPV0 (Cyclic) allows:
o
Start and shutdown.
o
Read parameters (write parameters are not allowed via DPV0).
DPV1 allows:
o
Everything that DPV0 allows
o
Change the cyclic parameters that display via DPV0.
o
Write to registers.
17.3
Description of the DPV0 (Cyclic) Frame:
From the Profibus controller to the HRVS-DN two bytes (16 bits) are transferred.
From the HRVS-DN to the controller 40 bytes are transferred.