162 • HRVS-DN Communication (Profibus protocol)
_____________________________________________________________________________________________
17.10
Stop Parameters
Parameter
#
Range
Default
Soft_Stop_Curve
40
0..11 (6..11 are for Tacho only) 1 (Standard)
Deceleration_Time 41
0..90
0
(Seconds)
Final_Torque 42
0..10
0
(Minimum)
Coast Down Delay
43
Off (9) 10..3600
9 (Off)
Reserved 43..47
17.11
Dual Adjust Parameters
Parameter
#
Range
Default
DA Initial Voltage /
DA Initial Current
48
10..80 % of full voltage /
100..400 % of FLA
30 /
100 % of FLA
DA Current Limit
49
100..700
400 % of FLA
DA Acceleration Time
50
1..90
10 (Seconds)
DA Deceleration Time
51
0..90
0 (Seconds)
DA Motor FLA
52
20..1800
150 (Amp.)
Reserved 53..55
17.12
Fault Parameters
Parameter
#
Range
Default
UV & PL Auto_Reset
56
0..1 (0 - No, 1 - Yes)
0 (No)
Under_Current_Reset
57
10..120 (&121=off)
121 (Off)
By-Pass_Open_Trip
58
0 / 1 (0 – Disable,1 - Enable)
1 (Enable)
Trip_after_By-Pass
59
0 / 1 (0 – Disable,1 - Enable)
1 (Enable)
By-Pass_Auto_Reset
60
0 – No, 1 – Yes
0 (No)
Set_Curve_To_0
61
0 / 1 (0 – Disable,1 - Enable)
1 (Enable)
Power On & No Start
62
0 / 1 (0 – Disable,1 - Enable)
1 (Enable)
Insulation_Alarm 63
1(Off) – 100 (10 Mohm)
1 (Off)
Insulation_Trip 64
1(Off) – 100 (10 Mohm)
1 (Off)
Phase Sequence
65
0 – Pos., 1 – Neg., 2 – Ignore
0 (Positive)
Reserved 66..71
17.13
I/O Programming
Parameter
#
Range
Default
Prog. Input #7 (thermal 7) 72
0..3
0 – Test
1 – Reset
2 – Multi Soft Stop - consult the
factory
3 – Current Control - consult the
factory
1 (Reset)
Prog. Input #8 (thermal 8) 73 0..1 (0=D.Adj.,1=Reset)
0 (Dual Adjust)
Fault Relay Type
74 0..1 (0=Fault, 1=Fault-Fail Safe) 0 (Fault)
Immediate Realy Type
75 0..1 (0=Immediate, 1=shear pin) 0 (Immediate)
Realy On Delay
76 0..3600
0 (Seconds)
Realy Off Delay
77 0..3600
0 (Seconds)
Analog output
78 0..1 (0 - Normal, 1 - Inverted)
0 (Normal)
Reserved 79
17.14
Communication Parameters
Parameter
#
Range
Default
Comm. Protocol
80
0 – Modbus, 1-Profibus
1 – Profibus
Modbus Baud Rate
81
12..96 (*100)
192 (19200 bps)
Parity Check
82
0/1/2 (Even / Odd / No)
0 (Even)
Profibus_Network
83
0..126 (0-Off)
0 (Off)
S. Link Parameters Save
84
0 (Disable), 1 (Enable)
0 (Disable saving)