135 • HRVS-DN Communication (ModBus Protocol)
_______________________________________________________________________________________________
16.7
Actual Data (3X References & 4X references)
Actual data includes measured values such as voltage, current and insulation resistance. It includes both
logic and statistical information. All parameters are
word
(two bytes) parameters. The protocol supports only
reading of these parameters.
Parameter # is "1 based". The actual parameter address is 1 lower than parameter #. For example the
address of parameter #1 is 0 (30000).
The parameters have double mapping, at the following
3x & 4x
references:
Note: Function 4 should be used to read 3x references and function 3 to read 4x references.
Parameter
# (3x) # (4x)
Comment
Logic Status
1
257
Logic status of HRVS-DN. 1 indicates:
d15: HRVS-DN Trip.
d14: Motor Stopped.
d13: Motor in Soft Stop Process.
d12: Motor in Start Process.
d11: Motor is Running.
d10: Motor is running with Closed By_Pass.
d9: Up_To_Speed. Like d10 and I reduced (once) below
115% of FLA.
d8: Reserved.
d7: Dual_Adjust On.
d6..d0: Reserved.
Note: After bypass is closed, trip (d15) and running (d11),
can be ON together. See Trip_after_By-Pass setting
parameter at fault parameters page.
Hardwired inputs
2
258
Discrete Hardwired control inputs:
d15..d8: Reserved.
d7: External fault 2, Terminal 20.
d6: External Fault 1,Terminal 19.
d5: Reserved.
d4:Programmable Input , Terminal 8
Programming options:
0-D.Adj / 1- Slow.Speed / 2-Reset
d3: Programmable Input, Terminal 7
Programming options:
0-Test1 / 1-Reverse / 2-Reset
d2: Start Input.
Terminal 6
d1: Soft Stop Input.
Terminal 5
d0: Stop Input.
Terminal 4
Relays
3
259
d0 - Immediate,d1- End Of Acc, d2 - Fault relay
Voltage
4
260
Line voltage, % of rated voltage.
I1_amp
5
261
Current of phase 1, Ampere.
I2_amp
6
262
Current of phase 2, Ampere.
I3_amp
7
263
Current of phase 3, Ampere.
Reserved
8 264
Dip_Switch
9
265
d15..d8: Reserved.
d7: Setting Lock
- (right-most)
d6: Enlarged Setting Ranges
d5: Language Selection.
d4: Language Selection.
d3: Reserved - Must be set to Off.
d2: Generator Starting - Set to Off.
d1: Tacho feedback available (1).
d0: Min (off) / Max display pages- (left most)
Phase_Sequence
10
266
1: Correct Phase seq. 0 : Wrong Phase Seq.
Motor Insulation R
11
267
Motor Insulation Resistance [KOhm]
Reserved
12..14 268..270