25 • Technical Data
_______________________________________________________________________________________________
Indication Description
Remarks
Terminal 7
Programmable input –
TEST / RESET/MULTI
SOFT STOP*
(MULTI SOFT STOP
applicable when special
software for multi soft stop
is ordered)
Refer to section
4.7.1 page 30.
Terminal 8
Programmable input –
DUAL ADJUSTMENT /
RESET
Refer to section
4.7.2 page 30.
Terminal 9
Common to terminals 4-8.
This terminal is a reference for terminals 4, 5, 6, 7
& 8.
Note:
When Control Supply and Control Input voltage are
from the same source, connect a jumper between
terminals 3 and 9.
Terminal 10
Programmable IMM/
# STRT PREAL (N.O.)
IMM/# STRT PREAL is the immediate/# of starts
pre-alarm output relay.
Terminal 11
Programmable IMM/
# STRT PREAL (N.C.)
Voltage free 8A, 250VAC, 2000VA max.
Selection between functions is made from the
keypad or through the communication.
Terminal 12
Programmable IMM/
# STRT PREAL (Common)
Refer to section
7.8.7 page 73 for IMM/ # STRT
PREAL programming.
Refer to section
4.7.3 page 30 for more details.
Terminal 13
Programmable Fault
Output relay (N.O.)
Voltage free 8A, 250VAC, 2000VA max. changes
its position upon fault.
Terminal 14
Programmable Fault
Output relay (N.C.)
The contact is programmable to function as FAULT
or FAULT-FAIL SAFE.
Terminal 15
Programmable Fault
Output relay (Common)
When the FAULT function is selected, the relay is
energized upon fault. The contact returns to its
original position when one of the following occurs:
The fault has been removed and HRVS-DN was
reset
Disconnection of Control Supply
When the FAULT-FAIL SAFE function is selected,
the relay is energized immediately when the
Control Supply is connected and de-energizes
when one of the following occurs:
Fault
Disconnection of Control Supply
Refer to section
7.8.7 page 73 for FAULT RELAY
TYPE programming.
Terminal 16
Programmable End of
Acceleration (Run) Output relay
(N.O.)
Voltage free 8A, 250VAC, 2000VA max. changes
its position at the end of acceleration, after an
adjustable time delay (Contact Delay), 0 – 120 sec.
Terminal 17
Programmable End of
Acceleration (Run) Output relay
(N.C.)
The contact returns to its original position on SOFT
STOP or STOP signals, on FAULT condition, or
upon voltage outage.
Terminal 18
Programmable End of
Acceleration (Run) Output
relay (Common)
The End of Acceleration contact (Run) can be used
for:
Closing a Bypass Contactor. Use an interposing
relay.
Activating a valve after compressor has reached
full speed
Loading a conveyor after motor reached full
speed.
Refer to section
7.8.3 page 60 for RUN CONTACT
DLY programming