138 • HRVS-DN Communication (ModBus Protocol)
_____________________________________________________________________________________________
16.8
Parameter Settings (4X References)
Parameter settings include all parameters that can be set manually. These parameters determine the modes
of operation of the HRVS-DN. They also set protections level. All parameters are word (two bytes)
parameters
.
The protocol supports both reading and modifying of (most of) these parameters.
Note: Use function 3 to read the setting parameters.
Any one of these parameters must be set with care. Inappropriate settings of some parameters can
result in damage to both the motor and the HRVS-DN.
The parameters have the following
4x
references:
Parameter
#
Range
Default
Main & protect. parameters
Rated
Line
Voltage
1
2300..15000
6600
(Volt.)
Starter
FLC
2
20..1800
150
(Amp.)
Motor
FLA
3
20..1800
150
(Amp.)
Rated
Motor
Power
4
50..40000
1000
(KW)
Service
Factor
5
100..130%
100
(%)
Undercurrent Trip
6
0..90
0 (% of FLA)
Undercurrent
Delay
7
1..40 10
(Seconds)
Overcurrent Shear Pin
8
100..850
850 (% of FLA)
Overcurrent
Delay
9
0..50 5
(0.5
Sec.)
Overload Class
10
IEC 5,10,15,20,25,30
IEC Class 10
NEMA
5,10,15,20,25,30
FLA)
Overload
Protect
11
0=Disable
1=Enable
While
Run
1=Enable
While
Run
2=Enable
Unbalance Trip
12
10..100, 101 = Off.
20 (%)
Unbalance
Delay
13
1..60
5
(Seconds)
Ground Fault Trip
14
10..100, 101 = Off.
20 (% of FLA)
Ground Fault Delay
15
1..60
5 (Seconds)
Undervoltage
Trip
16
50..90
70
(%)
Undervoltage
Delay
17
1..100
5
(Seconds)
Overvoltage
Trip
18
110..125
120
(%)
Overvoltage
Delay
19
1..10 2
(Seconds)
Reserved
20..24
Start Parameters
Soft Start Curve
25
0..11 (6..11 are for Tacho only) 1 (Standard).
Pulse Level
26
70 (%of FLA) – 700 (%of FLA) 70% of FLA
Pulse Time
27
0..10 (Tenth Seconds)
0 (No Pulse)
Initial
Voltage
28
10..80
30
(%
of
full
voltage)
Initial Current
28 !
100..400 % of FLA
100 % of FLA
Current
Limit
29
100..700
400
(%
of
FLA)
Acceleration
Time
30
1..90 10
(Seconds)
Max.
Start
Time 31
1..250
30
(Seconds)
Number Of Starts
32
1..10 & (11 = off)
1
Starts
Period
33
1..60 20
(Minutes)