Troubleshooting Dual-Meter
Connection
Troubleshooting Dual-Meter Connections
using SetApp
To verify the connectivity of two meters using SetApp, refer to
"Troubleshooting the Meter using SetApp" on page 43
Troubleshooting Dual-Meter Connections
using the Device Display
When two meters are connected on the same RS485 bus, the
following should appear in the Communication status screen:
w w w w w w w
D e v P r o t # #
R S 4 8 5 - 1 < M L T > < 0 2 > < 0 2 >
R S 4 8 5 - 2 < - - - > < - - > < - - >
Z i g B e e < - - - > < - - > < - - >
Device Type or Protocol are configured incorrectly
If <
MLT>
(multiple meters) is not displayed in the
Dev
field as
the device type, or <02> is not displayed in the
Prot
field as
the number of meters, configure the meters as follows:
1. Select
Communication
è
RS485
-x Conf
è
Device Type
è
Multi Devices
. Select
Device 1
or
Device 2
.
Energy Meter with Modbus Connection Installation Guide MAN-01-00269-1.5
62
Troubleshooting Dual-Meter Connection