Check for water damage or sealing problems:
Inspect the entire conduit run for possible points of
water penetration, and fix leaks.
Ensure that proper outdoor rated components are
used.
Troubleshooting the Meter using the
Device Display
Communication Status Screen
Troubleshooting
The communication status screen should display the following:
D e v P r o t # #
R S 4 8 5 - 1 < M T R > < S E > < 1 >
R S 4 8 5 - 2 < - - - > < - - > < - - >
Z i g B e e < - - - > < - - > < - - >
Device Type or Protocol are configured incorrectly
If
MTR
(meter) is not displayed as the device type (DEV), or
WN
(WattNode) is not displayed as the Prot (protocol),
configure the meter as follows.:
1. Select
Communication
è
RS485-x Conf
è
Device Type
è
Revenue Meter
.