UPS for 480 Vac Grid, User Guide, doc. rel. 4.0
72
Figure 48: Auto Correction screen
Auto Correction is enabled by default. This is the recommended setting for most
situations.
After performing any calibrations or adjustments the Auto Correction feature
should be re-enabled, for optimal system performance.
8.2.2.11.
POWER WALK-IN
At system startup, this parameter give you control of the time it takes to bring the system’s dc
voltage up to its nominal level. The module by default begins taking ac power from the impute
after 13 seconds. By adjusting the time value on the power walk in screen you increase the default
time in turn.