85
UPS for 480 Vac Grid, User Guide, doc. rel.4.0
8.2.4.1.1.
Battery test fault voltage
During the automatic scheduled battery test the dc voltage will try to drop to 235 Vdc (11.75 x
20 batteries per poll). If the batteries are unable to hold the minimum charge the battery test will
fail due to one of the batteries having a lower voltage than 11.75 V dc.
Figure 64: Battery Test Fault Voltage
Battery test failure will trigger a system alarm indicating requirement for battery
maintenance.
8.2.4.1.2.
Rectifier voltage during battery test
Sets the value to which the rectifier's output dc voltage descends during a battery test.