193
UPS for 480 Vac Grid, User Guide, doc. rel.4.0
Register
Variable name
GET Values
Remarks
348
4x0348
Shutdown Due To
Overload
0: Alarm off
1: Alarm on
349
4x0349
Shutdown Due To EPO
0: Alarm off
1: Alarm on
350
4x0350
One Module Not
Responding
0: Alarm off
1: Alarm on
351
4x0351
Static Switch Is Not
Responding
0: Alarm off
1: Alarm on
352
4x0352
All Ac modules Are Not
Responding
0: Alarm off
1: Alarm on
353
4x0353
Controller Adapter Is Not
Responding
0: Alarm off
1: Alarm on
354
4x0354
Load Above 90%
0: Alarm off
1: Alarm on
355
4x0355
Detected More Modules
Then Defined
0: Alarm off
1: Alarm on
356
4x0356
Fan Fault In One Of The
Ac modules
0: Alarm off
1: Alarm on
357
4x0357
Load On Battery (Input
AC Failure)
0: Alarm off
1: Alarm on
358
4x0358
Module Switching
Adaptor Is Not
Responding
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
359
4x0359
Module Switching
Adaptor Is Not Switching
0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
360
4x0360
More Than One Master
Module Detected
0: Alarm off
1: Alarm on
361
4x0361
AC Input Failure Page 1 0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
362
4x0362
AC Input Failure Page 2 0: Alarm off
1: Alarm on
Only for Mega modular UPS in 20 module
configuration
363
4x0363
Conflict In Nominal
Settings Of Ac modules
0: Alarm off
1: Alarm on
When output voltage or output frequency
settings are not the same on all attached Ac
modules
364
4x0364
Controller Battery Test
Failed
0: Alarm off
1: Alarm on
Not available on Mega modular UPS, since
there is no battery in the controller on this
model
365
4x0365
Inverter Is Out Of
Synchronization With
Mains
0: Alarm off
1: Alarm on
366
4x0366
Inverter Is Out Of
Synchronization With
Mains For Short Time
0: Alarm off
1: Alarm on