User Guide
Inverter-Charger Technical Data
Parameter
Vulcan 120
Vulcan 120 PRO
Vulcan 240
AC Output Power Rating
Single-Phase 120Vac, 2kW/3kW, 50Hz/60Hz,
4kW/6kW Peak
Single-Phase 240Vac,
2kW, 50Hz/60Hz, 4kW
Peak
Inverter Efficiency
92%
91%
Power Factor
0.9 - 1.0
Transfer Switch Rating
30A
Transfer Switch Speed
10ms/20ms
Inverter DC Cutoff
11.2V
Low AC Voltage Cutover
80Vac - 108Vac
170Vac - 220Vac
MPPT Charge Controller
4
150Vdc @ 35A (500W)
AC-to-DC Charger
Power Factor Corrected 120Vac/250Vac @ 360W
Advanced BMS Type
200A, 10.8V Cutoff, Hi/Lo Temp, Overcurrent & Short Circuit Protection
Internal Battery Type
1.4kWh Lithium Iron Phosphate (LiFePo4)
Useful Battery Capacity
97Ah/1.236kWh
96Ah/1.223kWh
Scalable Battery Capacity
5kWh - >100kWh
AC Output Receptacle
Type
3 - NEMA 5-15R/5-20R/
4 - Cooper Red, NEMA
5-20R Hospital Grade
5
1 - NEMA L5-30R, 3 -
NEMA 5-20R
1 - NEMA L6-30R
AC Input Plug Type
1 - NEMA 5-15P/5-20P
1 - NEMA L5-30
1 - NEMA L6-30P
Solar Input Connection
2 - MC4 Terminated, 8' 10 AWG Cables
Battery Expansion
Yes. Hot swappable with 180A Quick Connectors.
Optional Voltage
Configurations
108, 110 & 120V @ 50Hz/60Hz
5kVA Transformer
120V/240V, 50Hz/60Hz
Expansion Connector
Amphenol 180A/1000V Heavy Duty Power Connector, ATHP041P08NN-50
Cooling
2 - Variable and 2 - Fixed Speed DC Fans
Operating Temperature
-20ºC/-4ºF to 122ºF/50ºC, with output derated above 104°F (40°C)
Heating Option
20W Heating Element: On @ 5ºC/41ºF, Off @ 15ºC/60ºF
Design Life
10 Years
Ingress Protection
IP50
Dimensions
25'D x 15.75'H x 8.27'W (635mm x 400mmm x 210mm)
Weight
55lbs
5
Heavy duty Cooper, red, hospital grade 20A receptacles with 20A inlet plug available upon request.
4
650W (150V/45A) Charge controller upgrade or charge controller delete is available upon request.
Battery Energy Storage and Power Solutions
© Sol Donum
™
2022
39