background image

Figure 20: Example of

Radar” application table

4.9

Operation of the WB169-SI2 module

The WB169-SI2 module performs broadcasting of radio messages fully automatically. Take into consideration that
the broadcasting systems according to the Wireless M-BUS standard has no protection against interference during
transmission (a signal collision, which occurs when two modules broadcast at the same time), so that temporary
loss of data from some modules can commonly occur in case of operating of a large number of modules in one radio
network. These losses can last for several hours or days.

The greatest risks of permanent breakdown of module broadcasting are commonly caused by human activities within
the installation. It is mainly about the following risks:

temporary or permanent shading of the antenna (e.g. due to building operations);

mechanical damage of the module, the antenna cable or the antenna when handling things at the installation
site.

To eliminate these risks, it is recommended to pay close attention to selection of the installation site and choice of
antenna and antenna location so that to find appropriate compromise between qualities of signal and the level of
risk of mechanical damage of the module or antenna. It is necessary to carry out the installation carefully with
using of high-quality cables and mounting components.

To prevent an unexpected breakdown, it is recommended to perform regular monitoring of all broadcasting data,
i.e. readings, processor temperature and battery voltage. If some of the parameters goes beyond the common steady
value, it is recommended to contact the installation site caretaker and ask for the potential cause of the anomaly
or perform the physical check on the installation site.

4.10

Using of WB169-SI2 module for remote monitoring of sensors

The WB169-SI2 module can be used also for remote monitoring of any two-state sensors with either isolated contact
(e.g. mechanical contact, relay, reed contact...), or solid-state relay, or open collector types of outputs. It is not
possible to connect a sensor with its own source of voltage on its output. Convenient types of sensors are displayed
in the Figure

21

.

When using of sensor with

open collector” output (see

optocoupler” in the Figure

21

left), it is necessary to

observe its +/- polarity as marked on the module’s and sensor’s labels. When using of sensors with solid state
relay output (see Figure

21

in the middle), or with isolated contact (see Figure

21

right), the polarity is usually not

important.

Sensor output should be connected to the module’s input clamps same way, as consumption meter. It is recom-
mended to use shielded cable with minimum length.

WB169-SI2

37

Summary of Contents for WB169-SI2

Page 1: ...WIRELESS COMMUNICATION SYSTEM Wireless M BUS WB169 SI2 Revision 1 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Page 2: ...for RF subsystem diagnostics 20 3 1 12 Commands of Utils group for setting of module common functions 20 3 1 13 Overview of module configuration parameters 22 3 2 Setting of parameters by using of opt...

Page 3: ...le 24 10 Basic forms of WB169 SI2 module in SOFTLINK Configurator application 27 11 Input output setting form and form for setting of encryption 28 12 View of WB169 SI2 module information message rece...

Page 4: ...appointed element of the radio network repeater or slave with such functionality Each repeated message is marked as repeated message so as not to be repeated again 1 2 Module usage The WB169 SI2 modul...

Page 5: ...g of opening closing of overhead doors of halls where the module can provide information about current status of each door and measure number of open close cycles of the doors Another example is monit...

Page 6: ...red remote control with using of optical converter The module is equipped with the circular crater shaped pit that supports magnetic fixing of optical converter with holding on magnet in right positio...

Page 7: ...ce Transmission speed 115 200 Baud Optical I F specification complies with IrPHY 1 4 standard Pulse sensor inputs Resistance of released contact more than 10 M Resistance of short circuited contact le...

Page 8: ...acoSystem product family devices The description and meaning of the parameters that can be changed by optical converter can be found in the section 3 2 Setting of parameters by using of optical conver...

Page 9: ...S version 0 255 medium Show or set MBUS medium 0 255 periode Change periode of send 0 disable 0 periode in minutes 0 from input mode Set WMBUS mode 1 N1 2 N2 chan Set WMBUS channel type for help ekey...

Page 10: ...s configuration parameters it does so only in operating configuration If the current operating configuration was not stored to FLASH memory the module returns to the saved configura tion after reset I...

Page 11: ...mmunication mode 1 N1 mode 2 N2 mode chan setting of frequency channel choice from 7 options ekey setting of encryption key encryption disabled Variable M BUS ID is a serial number of the device in M...

Page 12: ...info XYZ cfg Maximum length of the string is 29 characters The only basic set of characters can be used without diacritics It is not recommended to change this parameter Periode command serves for set...

Page 13: ...for transmitting power 27 dBm 500 mW An example of checking setting and re checking of transmitting power cfg power MBUS power 3 20 dBm cfg power 5 MBUS power changed from 3 to 5 27 dbm cfg power MBU...

Page 14: ...is set to the module s configuration an information Data will be encrypted by AES displays in the list of configuration parameters see chapter 3 1 1 Encryption can be switched off by setting of dot p...

Page 15: ...coming pulse Actual counter value can be displayed by using of val index command without parameter Counter status can be set to required value by using of val index command followed by required whole...

Page 16: ...0 If it is needed to get volume in other units than litres e g in m3 or other quantity than volume is measured e g electrical work in kWh it is necessary to adjust values of multiplier and divisor to...

Page 17: ...t 1000 x Wh unit is presented as 1000 000 Wh By using of det index command a trigger edge of the counter could be chosen If it is preset to 0 option default setting the value of counter will increase...

Page 18: ...ume If there are any leaks time intervals with zero consumption practically either do not occur or there are only short intervals caused by discontinuity of measuring system e g if one metering pulse...

Page 19: ...in the consumption of gas water or other liquids when the burst consumption caused by broken pipe or similar fatal failure of distribution system occurs If the consumption of liquid gas is abnormally...

Page 20: ...es in normal operation e g during filling a tank with water but in the same time it will prolong the response time between the breakdown and sending of alarm Setting of Burst alarm function parameters...

Page 21: ...atus after transition value is 0 or 1 and a relevant port identifi cation coded into DIF code as follows status of 0 input DIF 31 status of 1 input DIF 71 VIF code is alway set to FD 3A value that in...

Page 22: ...ching function activated all input pulses are carried only to the first input The second physical input is connected to the tariff switching control voltage see figure 7 Input pulses from the first po...

Page 23: ...eration Using of these commands can cause inoperability of the device 3 1 12 Commands of Utils group for setting of module common functions This group of commands is intended for control and setting o...

Page 24: ...follows cfg time 0x182555 RTC time 18 25 55 2019 01 30 systime 1548869155 2019 01 30 18 25 55 01 cfg date 0x190128 RTC time 18 26 58 2019 01 28 systime 1548696418 2019 01 28 18 26 58 01 cfg As it is...

Page 25: ...command can be used during installation and testing of the module An example of the command for sending of series of 5 messages mon sendp 5 send 5 msgs mon The command reset performs the module reset...

Page 26: ...t 0 65535 Alarm limit value Burst function 0 17 Burst periode 0 1090 Burst check time Burst function 0 18 Radio Power 1 5 Transmitting power 5 19 Comm mode 1 2 Communication mode 1 N1 20 Channel 1 7 F...

Page 27: ...the module s cover This is the significant advantage especially if the module is used in humid environment and has been sealed by additional silicon filling additional adaptation for IP 68 proofing An...

Page 28: ...ditable for the WB169 SI2 it is an editable part of full meter sensor M Bus identification the default value of the Medium parameter is 07 Water More detailed description of the variable and possibili...

Page 29: ...for setting of counter trigger edge Falling option means that the counter value will increase with falling edge of measuring pulse i e short circuiting of mechanical contact or 1 to 0 transition of el...

Page 30: ...details in section 3 1 11 Modem group commands The WMBUS Mode parameter can be used for selection of the module s WMBUS communication mode Factory setting is N1 mode variable is entered by choosing f...

Page 31: ...d information message with status of all variables broadcasted periodically short alarm message sent immediately when alarm status has been detected 3 3 1 Iinformation message Information message of t...

Page 32: ...e AES 128 data encryption is switched on there are two additional Figure 12 View of WB169 SI2 module information message received by WMBUSAN4 analyzer control segments inserted before data segments of...

Page 33: ...s Positive events of NO LEAK NO BURST type are generated in that case when after one or several alarm periods a period without alarm status came around Each alarm message has Wireless M BUS header WMB...

Page 34: ...information about the current status of sensor input counter i e number of transitions since last counter reset The DIF and VIF values correspond with setting of given input transferred data value Val...

Page 35: ...ischarging current increases in low temperature the battery capacity reduces frequency of radio transmitting Modules are delivered with preset period of regular transmitting of info messages as stated...

Page 36: ...30 C To prevent the unwanted discharging of internal battery it is recommended storing the modules with batteries disconnected and activate the battery during mounting with exception of modules with a...

Page 37: ...the module to a suitable firm object wall pipe by two screws or by a clamping tape There are mounts by the box sides for the attachment The recommended position of the mounted module is in the way th...

Page 38: ...rea of installation as well as protection of the device against possible mechanical damage The radio signal conditions can be estimated empirically on the base of previous experience or examined by me...

Page 39: ...meter 4 7 Module dismantling When dismantling open the module disconnect cables and dismantle the cap from the wall pad or pipe Switch the battery off and put the module parts back together put the ca...

Page 40: ...is necessary to carry out the installation carefully with using of high quality cables and mounting components To prevent an unexpected breakdown it is recommended to perform regular monitoring of al...

Page 41: ...t segment In this case the primary cause of alarm status should be opening of security loop that causes detachment of contact head from magnet and releasing of reed contact inside the head Releasing o...

Page 42: ...k functionality of the new module If the new device works properly label the original module as defective and fill in the appropriate documentation prescribed by internal rules for this case 5 1 3 Tra...

Page 43: ...ctionality of cable connection by ohm meter If there is a problem with reliability of the connection or the cable is evidently damaged replace the cable immediately 3 check whether the cable is correc...

Page 44: ...h meters 2 No data are available from only one meter sensor connected to the WB169 SI2 module In this case it is recommended to check functionality of the module subsystems in following order check fu...

Reviews: