background image

Example of setting

Leak detection period”

parameter for port No 1 (index ”0”) to 24 hours value:

cfg#leakp 0 24

Value[0] changed from 0 to 24

cfg#

Detection period can be set in range of 1 - 1090 hours, typical setting is 24 hours (daily operational cycle), or 168
hours (weekly operational cycle). Detection period starts running from module restart, or from the moment when
the parameter is changed. Alarm message is sent at the end of detection period.

Example of setting

Zero period”

parameter for port No 1 (index ”0”) to 60 minutes value:

cfg#leakz 0 90

Value[0] changed from 0 to 90

cfg#

Zero consumption period can be set in range of 1 - 1090 minutes with precision of ten minutes (rounded to tens of
minutes, e.g. 10, 20, 30...). If the command is entered with any other value (e.g. 36 minutes) the system will store
rounded value anyway (in this case 40 minutes). General principle is that setting of zero period parameter to longer
values means that the detection is more sensitive (it is capable to detect smaller leaks), but it is also less reliable
with higher probability to produce false alarm due to real consumption caused by random changes of operating
cycle (e.g. if somebody was held up at work few hours longer).

Setting of

Leak” alarm function parameters appears in the List of configuration parameters (

show” command),

in the section of the particular port:

MBUS value[0] DIB : 04 00, VIB : 13 00 ,multiplier 1, divider 1

Leak detection period 24 hour(s), zero period 90 minutes

Structure of alarm message of

Leak” type is described in the paragraph

3.3.2

Alarm message”.

3.1.8

Description and setting of

Burst” alarm function

Burst” function is used for detection of such situations in the consumption of gas, water or other liquids, when the

burst consumption caused by broken pipe (or similar fatal failure of distribution system) occurs. If the consumption
of liquid/gas is abnormally huge for some period of time, the module transmits to the superior system alarm message
of ”7” type (

Burst”).

Burst” function principle is shown in the figure

5

.

Burst” alarm function is set-up by entering of the

burst

consumption limit

(”burstp[index]” command), that means the limit over which the consumption is considered

as abnormal, and entering of

Burst Check Time” period

(”burstt[index]” command) that means the minimum

time period during which the consumption must be permanently over limit to detect the

Burst” alarm.

In view of the fact that different meters connected to the module could have different conversion rate of volume per
measuring pulse, consumption limit is delimited universally as

number of registered pulses per 10 minutes

time period

. Conversion table between

pulses per 10 minutes” and

consumption per minute” for frequently

used conversion rates of watermeters is available in the figure

6

.

Burst” function can be activated for chosen port by using of

”burstp[index”]

command that defines required

consumption limit in number of pulses per 10 minutes period. By using of

”burstt[index]”

command setup

concurrently for the same port minimum duration of abnormal consumption (

Burst Check Time”) in minutes. If

one of these parameters is set to ”0” for some port,

Burst” function is deactivated for that port.

Example of setting

LIMIT”

parameter for port No 1 (index ”0”) to 15 pulses per 10 minutes:

cfg#burstp 0 15

Value[0] changed from 0 to 15

cfg#

Consumption limit alarm value can be set in practically unlimited range (1 to 65535 pulses per 10 minutes).

Example of setting

Burst Check Time”

parameter for port No 1 (index ”0”) to 40 minutes value:

WB169-SI2

16

Summary of Contents for WB169-SI2

Page 1: ...WIRELESS COMMUNICATION SYSTEM Wireless M BUS WB169 SI2 Revision 1 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Page 2: ...for RF subsystem diagnostics 20 3 1 12 Commands of Utils group for setting of module common functions 20 3 1 13 Overview of module configuration parameters 22 3 2 Setting of parameters by using of opt...

Page 3: ...le 24 10 Basic forms of WB169 SI2 module in SOFTLINK Configurator application 27 11 Input output setting form and form for setting of encryption 28 12 View of WB169 SI2 module information message rece...

Page 4: ...appointed element of the radio network repeater or slave with such functionality Each repeated message is marked as repeated message so as not to be repeated again 1 2 Module usage The WB169 SI2 modul...

Page 5: ...g of opening closing of overhead doors of halls where the module can provide information about current status of each door and measure number of open close cycles of the doors Another example is monit...

Page 6: ...red remote control with using of optical converter The module is equipped with the circular crater shaped pit that supports magnetic fixing of optical converter with holding on magnet in right positio...

Page 7: ...ce Transmission speed 115 200 Baud Optical I F specification complies with IrPHY 1 4 standard Pulse sensor inputs Resistance of released contact more than 10 M Resistance of short circuited contact le...

Page 8: ...acoSystem product family devices The description and meaning of the parameters that can be changed by optical converter can be found in the section 3 2 Setting of parameters by using of optical conver...

Page 9: ...S version 0 255 medium Show or set MBUS medium 0 255 periode Change periode of send 0 disable 0 periode in minutes 0 from input mode Set WMBUS mode 1 N1 2 N2 chan Set WMBUS channel type for help ekey...

Page 10: ...s configuration parameters it does so only in operating configuration If the current operating configuration was not stored to FLASH memory the module returns to the saved configura tion after reset I...

Page 11: ...mmunication mode 1 N1 mode 2 N2 mode chan setting of frequency channel choice from 7 options ekey setting of encryption key encryption disabled Variable M BUS ID is a serial number of the device in M...

Page 12: ...info XYZ cfg Maximum length of the string is 29 characters The only basic set of characters can be used without diacritics It is not recommended to change this parameter Periode command serves for set...

Page 13: ...for transmitting power 27 dBm 500 mW An example of checking setting and re checking of transmitting power cfg power MBUS power 3 20 dBm cfg power 5 MBUS power changed from 3 to 5 27 dbm cfg power MBU...

Page 14: ...is set to the module s configuration an information Data will be encrypted by AES displays in the list of configuration parameters see chapter 3 1 1 Encryption can be switched off by setting of dot p...

Page 15: ...coming pulse Actual counter value can be displayed by using of val index command without parameter Counter status can be set to required value by using of val index command followed by required whole...

Page 16: ...0 If it is needed to get volume in other units than litres e g in m3 or other quantity than volume is measured e g electrical work in kWh it is necessary to adjust values of multiplier and divisor to...

Page 17: ...t 1000 x Wh unit is presented as 1000 000 Wh By using of det index command a trigger edge of the counter could be chosen If it is preset to 0 option default setting the value of counter will increase...

Page 18: ...ume If there are any leaks time intervals with zero consumption practically either do not occur or there are only short intervals caused by discontinuity of measuring system e g if one metering pulse...

Page 19: ...in the consumption of gas water or other liquids when the burst consumption caused by broken pipe or similar fatal failure of distribution system occurs If the consumption of liquid gas is abnormally...

Page 20: ...es in normal operation e g during filling a tank with water but in the same time it will prolong the response time between the breakdown and sending of alarm Setting of Burst alarm function parameters...

Page 21: ...atus after transition value is 0 or 1 and a relevant port identifi cation coded into DIF code as follows status of 0 input DIF 31 status of 1 input DIF 71 VIF code is alway set to FD 3A value that in...

Page 22: ...ching function activated all input pulses are carried only to the first input The second physical input is connected to the tariff switching control voltage see figure 7 Input pulses from the first po...

Page 23: ...eration Using of these commands can cause inoperability of the device 3 1 12 Commands of Utils group for setting of module common functions This group of commands is intended for control and setting o...

Page 24: ...follows cfg time 0x182555 RTC time 18 25 55 2019 01 30 systime 1548869155 2019 01 30 18 25 55 01 cfg date 0x190128 RTC time 18 26 58 2019 01 28 systime 1548696418 2019 01 28 18 26 58 01 cfg As it is...

Page 25: ...command can be used during installation and testing of the module An example of the command for sending of series of 5 messages mon sendp 5 send 5 msgs mon The command reset performs the module reset...

Page 26: ...t 0 65535 Alarm limit value Burst function 0 17 Burst periode 0 1090 Burst check time Burst function 0 18 Radio Power 1 5 Transmitting power 5 19 Comm mode 1 2 Communication mode 1 N1 20 Channel 1 7 F...

Page 27: ...the module s cover This is the significant advantage especially if the module is used in humid environment and has been sealed by additional silicon filling additional adaptation for IP 68 proofing An...

Page 28: ...ditable for the WB169 SI2 it is an editable part of full meter sensor M Bus identification the default value of the Medium parameter is 07 Water More detailed description of the variable and possibili...

Page 29: ...for setting of counter trigger edge Falling option means that the counter value will increase with falling edge of measuring pulse i e short circuiting of mechanical contact or 1 to 0 transition of el...

Page 30: ...details in section 3 1 11 Modem group commands The WMBUS Mode parameter can be used for selection of the module s WMBUS communication mode Factory setting is N1 mode variable is entered by choosing f...

Page 31: ...d information message with status of all variables broadcasted periodically short alarm message sent immediately when alarm status has been detected 3 3 1 Iinformation message Information message of t...

Page 32: ...e AES 128 data encryption is switched on there are two additional Figure 12 View of WB169 SI2 module information message received by WMBUSAN4 analyzer control segments inserted before data segments of...

Page 33: ...s Positive events of NO LEAK NO BURST type are generated in that case when after one or several alarm periods a period without alarm status came around Each alarm message has Wireless M BUS header WMB...

Page 34: ...information about the current status of sensor input counter i e number of transitions since last counter reset The DIF and VIF values correspond with setting of given input transferred data value Val...

Page 35: ...ischarging current increases in low temperature the battery capacity reduces frequency of radio transmitting Modules are delivered with preset period of regular transmitting of info messages as stated...

Page 36: ...30 C To prevent the unwanted discharging of internal battery it is recommended storing the modules with batteries disconnected and activate the battery during mounting with exception of modules with a...

Page 37: ...the module to a suitable firm object wall pipe by two screws or by a clamping tape There are mounts by the box sides for the attachment The recommended position of the mounted module is in the way th...

Page 38: ...rea of installation as well as protection of the device against possible mechanical damage The radio signal conditions can be estimated empirically on the base of previous experience or examined by me...

Page 39: ...meter 4 7 Module dismantling When dismantling open the module disconnect cables and dismantle the cap from the wall pad or pipe Switch the battery off and put the module parts back together put the ca...

Page 40: ...is necessary to carry out the installation carefully with using of high quality cables and mounting components To prevent an unexpected breakdown it is recommended to perform regular monitoring of al...

Page 41: ...t segment In this case the primary cause of alarm status should be opening of security loop that causes detachment of contact head from magnet and releasing of reed contact inside the head Releasing o...

Page 42: ...k functionality of the new module If the new device works properly label the original module as defective and fill in the appropriate documentation prescribed by internal rules for this case 5 1 3 Tra...

Page 43: ...ctionality of cable connection by ohm meter If there is a problem with reliability of the connection or the cable is evidently damaged replace the cable immediately 3 check whether the cable is correc...

Page 44: ...h meters 2 No data are available from only one meter sensor connected to the WB169 SI2 module In this case it is recommended to check functionality of the module subsystems in following order check fu...

Reviews: