HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 40 -
Overvoltage 1(V>)
265V
1s
2s
Overvoltage 2(V>>)
275V
-
0.2s
Region
Australia A
Australia B
Australia C
New Zealand
Under-
frequency 1
(F<)
Protective
function limit
value
47Hz
47Hz
45Hz
45Hz
Trip
delay
time
1s
1s
5s
1s
Maximum
disconnection
time
2s
2s
6s
2s
Over-
frequency 1
(F>)
Protective
function limit
value
52Hz
52Hz
55Hz
55Hz
Trip
delay
time
-
-
-
-
Maximum
disconnection
time
0.2s
0.2s
0.2s
0.2s
Default volt-watt settings for different regions are shown in the following table:
Region
Default value
V
W1
V
W2
Australia A
Voltage
253V
260V
Inverter maximum active power output level (P) %
of
S
rated
100%
20%
Australia B
Voltage
250V
260V
Inverter maximum active power output level (P) %
of
S
rated
100%
20%
Australia C
Voltage
253V
260V
Inverter maximum active power output level (P) %
of
S
rated
100%
20%
Default volt-var settings for different regions are shown in the following table:
Region
Default value
V
V1
V
V2
V
V3
V
V4
Australia A
Voltage
207V
220V
240V
258V
Inverter reactive power
level (Q) % of
S
rated
44%
supplying
0%
0%
60%
supplying
Australia B
Voltage
205V
220V
235V
255V
Inverter reactive power
level (Q) % of
S
rated
30%
supplying
0%
0%
40%
supplying