HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 39 -
002
000
Australia (Australia A)
003
Brazil 254
008
Australia-B
029
000*
Slovakia VSD
009
Australia-C
001*
Slovakia SSE
003
000
Spain RD1699
002*
Slovakia ZSD
004
000*
Turkey
033
000*
Ukraine
005
000
Denmark
034
000
Norway
001
Denmark TR322
001
Norway-LV
006
000*
Greece Continent
035
000
Mexico LV
001*
Greece island
038
000
Wide-Range-60Hz
007
000*
Netherland
039
000*
Ireland EN50438
008
000*
Belgium
040
000
Thailand PEA
009
000
UK G59/G99
001
Thailand MEA
001
UK G83/G98
042
000
LV-Range-50Hz
010
000
China
044
000
South Africa
001
China Taiwan
046
000*
Dubai DEWG
011
000*
France
001
Dubai DEWG MV
001
France FAR Arrete23
107
000*
Croatia
012
000
Poland
108
000*
Lithuania
013
000
Austria Tor Erzeuger
014
000
Japan
018
000
EU EN50438
001*
EU EN50549
019
000
IEC EN61727
020
000
Korea
021
000
Sweden
022
000
Europe General
For Australian Market:
For compliance with AS/NZS 4777.2:2020 please select from
002-000 Australia A (Australia Region A)
002-008 Australia B (Australia Region B)
002-009 Australia C (Australia Region C)
Please contact your local grid operator regarding which option to select
Note: Selecting 002-000 Australia A, 002-008 Australia B, 002-009 Australia C
will load the default power quality response mode and grid protection settings for
Australia Region A, B,C respectively.
Default grid settings for different regions are shown in the following table:
Protective function
Protective function
limit
Trip delay time
Maximum
disconnection time
Undervoltage 2(V<<)
70V
1s
2s
Undervoltage 1(V<)
180V
10s
11s