HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 32 -
Reflux Power = Export Power
Hard Anti-Reflux control = Hard Export limit control
Anti-Reflux Control = Soft Export limit control
When Anti-Reflux function is enabled, the reflux power of point of common
coupling (PCC) will be limited to the set Reflux Power limit.
Both Hard Anti-Reflux Control and Anti-Reflux Control can be used together.
However, when Hard Anti-Reflux control is enabled, Anti-Reflux power limit
cannot exceed the Hard Anti-Reflux power limit. The limit value is reported to
overload protection.
When communication signal with the electricity meter is lost, the output power of
the inverter is limited to the value of soft export limit and does not enter the state of
fault protection. When Hard anti reflux control is enabled, a loss of communication
with the meter will cause the inverter to enter into a fault protection state.