HYD 3K~6K-EP
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 17 -
4. Electrical Connections
Before performing electrical connections, ensure that the DC switch is OFF. Since
the stored electrical charge remains in a capacitor after the DC switch is turned OFF.
So it’s necessary to wait for at least 5 minutes for the capacitor to be electrically
discharged.
HYD 3K~6K-EP inverter is intended to be used in PV system with battery storage.
If not used as intended, the protection provided by the equipment may be impaired.
Installation and maintenance of inverter, must be operated by
professional electrical engineer.
Wear rubber gloves and protective clothing (protective glasses and
boots) when working on high voltage/high current systems such as
inverter and battery systems.
Attention
PV modules generate electric energy when exposed to sunlight
and can create an electrical shock hazard. Therefore, before
connecting DC input power cable, cover PV modules using
opaque clot.
Danger
For HYD 3K~6K-EP, open-circuit voltage (Voc) of module arrays
connected in series must be ≤ 580V.
Note
The connected PV modules must have an IEC 61730 Class A ratin
Table 4-1 Relevant current parameters of each model
Model
IscPV(absolute
maximum)
Maximum output over current
protection
HYD 3000-EP
18A/18A
15A
HYD 3680-EP
16A
HYD 4000-EP
20A
HYD 4600-EP
20.9A
HYD 5000-EP
21.7A
HYD 5500-EP
25A
HYD 6000-EP
27.3A
NOTE:
The DVC is the voltage of a circuit which occurs continuously between
any two live part in the worst-case rated operating condition when used as