32
ITYS PRO
10-15-20 kVA - Ref.: IOMITYPRXX00-EN 03
ADC+SL CARD
The ADC+SL (Advanced Dry C Serial Link) is a optional slot board that provides 4 relays for external device activation, 3
free inputs to report external contacts to UPS and one connector for external temperature sensor. There is also an RS485 insulated
serial link that provides MODBUS RTU protocol. A maximum of two cards can be installed on each unit.
This card can be configured to control four outputs and three digital inputs. The first output can be configured as normally open
(NO) or normally closed (NC). The other three outputs are configured as normally open (NO).
Available configurations:
OPTIONS SUPERVISOR
DIP1:ON - DIP2:OFF
IN/OUT Description
Filter (s)
In1
UPS Power Off
1
In2
Fan Failure
10
In3
Battery disconnected
10
Out1
General Alarm
10
Out2
Battery Discharging
30
Out3
Redundancy lost
10
Out4
Battery disconnected
1
ENVIROMENTAL
DIP1:ON - DIP2:ON
IN/OUT Description
Filter (s)
In1
UPS Power Off
1
In2
Programmable Alarm
10
In3
Battery Temperature Alarm
10
Out1
General Alarm
10
Out2
Battery Temperature Alarm
10
Out3
Overload or Redundancy lost
10
Out4
Programmable Alarm
10
SAFETY
DIP1:OFF - DIP2:ON
IN/OUT Description
Filter (s)
In1
UPS Power Off
1
In2
Insulation Fault
1
In3
Charger Disable/Enable
1
Out1
General Alarm
10
Out2
UPS Power Off activated
1
Out3
Battery Low or Imminent UPS stop alarm
10
Out4
Insulation Fault (A026)
1
NOTE!
For further information refer to the ADC+SL manual.
NET VISION CARD
NET VISION
is a communication and management interface designed for business networks. The UPS behaves exactly like a
networked peripheral, it can be managed remotely, and allows the shutdown of network workstations.
NET VISION
allows a direct interface between the UPS and LAN network avoiding dependence on the server and support SMTP,
SNMP, DMCP and many other protocols. It interacts via the web browser.
SOFTWARE OPTION
Visit www.socomec.com and enter
DOWNLOAD > SOFTWARE > UPS SOFTWARE
to find the communication software suitable
for your requirements.
NOTE!
Before making any operation, check that the software is compatible with your UPS model.