47
EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
CUSTOM ADC+SL CONFIGURATION FOR REMOTE SIGNAL BOX MANAGEMENT
In addition to the four standard configurations a customized configuration is available to manage the remote
SIGNALLING BOX OPTION.
SIGNALLING BOX OPTION configuration
IN/OUT
DESCRIPTION
ACTIVATION
DELAY (s)
REMARK
(1)
INPUT TYPE
STATE
IN1
UPS POWER OFF
1
Command sent to UPS
(2)
Close to activate
Normally open
IN2
NOT USED
-
-
IN3
NOT USED
-
-
RELAY 1
REQUEST TECHNICAL AS-
SISTANCE
1
Relating to a list of technical alarms
Normally closed
RELAY 2
BATTERY DISCHARGING
10
Relating to A019
Normally open
RELAY 3
END OF BACK-UP TIME
1
Relating to A017
Normally open
IMMINENT STOP
Relating to A000
RELAY 4
NORMAL OPERATION
1
Relating to S000
Normally open
1. The acronyms mentioned are linked to MODBUS table (Snnn=Status/Annn=Alarm).
2. A self-locking emergency push button must be used for the UPS Power Off input.
RS485 SERIAL LINK
• Insulated RS485, protected against over voltage. Only for local bus purposes; maximum ~500 m.
• Pull up and pull down line resistor XJ1 (failsafe biasing): jumper open by default.
• Possibility of fixing the RS485 cable to the board.
• Cable type required: twister pair cable + shield to connect to ground. (AWG 24, 0.2 mm
2
for example).
The INPUT and RELAYS are managed with information coming from the UPS.
NOTE!
Inputs and relays can be re-programmed depending on requirements.
Contact your SOCOMEC after-sales service to change Input/Output programming.
Information coming from inputs can be reported in the UPS database for display on the mimic panel and is accessible
on the MODBUS table.
The UPS can manage up to two ADC+SL option cards. The cards can be re-programmed for other uses.
In this specific case, the 2 serial links (SLOT 1 and SLOT 2) are independent.