Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
8. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care-
fully.
NOTE: with the stop procedure the load will be disconnected.
8.1 SWITCHING ON
• Connect the mains to the UPS.
• Put switch
Q1
(or the external input mains switching device) into position
1
.
• Wait for the display to switch on.
• Enter
MAIN MENU > COMMANDS > UPS PROCEDURES
.
• Select
Automatic Start Procedure
and press
ENTER
.
• Carry out the operations indicated on the display.
8.2 SWITCHING OFF
This operation interrupts the power supply to the load. The UPS and the battery charger will be shutdown.
• Enter menu
MAIN MENU > CONTROLS > UPS PROCEDURE
.
• Select
Automatic Stop Procedure
and press
ENTER
.
• Wait approx. 2 minutes for the UPS shutdown.
NOTE: the controlled shutdown of each server connected to the LAN can be managed by shut-
down software (only with Net Vision option card).
• Carry out the operations indicated on the display. This operation cannot be aborted.
8.3 BYPASS OPERATIONS
Available only with external manual bypass.
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part.
This operation is performed in the event of:
- standard maintenance.
- serious failure has occurred.
WARNING! This operation interrupts temporarily the power supply to the load.
WARNING! LOAD POWERED BY INPUT MAINS!
Your load is exposed to mains disturbances.
• Enter menu
MAIN MENU > CONTROLS > UPS PROCEDURE
.
• Select
Automatic Stop Procedure
and press
ENTER
.
• Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- put the switch to position 1.