48
EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
MODBUS SERIAL LINK
The RS485 provides MODBUS RTU protocol.
The description of MODBUS addresses and UPS database are described in the MODBUS user manual. All manuals
are available on SOCOMEC’s web site (www.socomec.com).
SERIAL LINK SETTINGS
COM1 relates to serial port on board in SLOT 1.
COM2 relates to serial port on board in SLOT 2.
Settings are available via the mimic panel to configure:
• Baud rate: 2400, 9600, 19200.
• Parity: None, Even, Odd.
• MODBUS slave number: 1 to 32.
BOARD STATUS
Board presence is reported through status S064 for slot 1 and S065 for slot 2.
In the case of board failure, ‘Option board alarm’ (A062) occurs to prevent malfunctioning.
10.1.1 TEMPERATURE SENSOR
The temperature sensor can be used to monitor the battery temperature.
The ADC+SL card can be ordered with or without the temperature sensor in kit.
If the sensor is present, temperature values are available on MODBUS protocol at following addresses:
Temperature board
Slot 1
0xn0AF
(1)
Format ##
Slot 2
0xn0AE
(1)
Format ##
1. n = unit number
Temperature range: 0 °C to 40 °C.